Troubleshooting Without Fault Display

Note:
Make sure that you use a keypad that has a flash number of 1004 or later. Keypads that have a flash number of 1003 or earlier will not show
characters correctly.
If the drive or motor operate incorrectly, but the keypad does not show a fault or error code, refer to the items this
section.
• Motor hunting and oscillation
• Unsatisfactory motor torque
• Unsatisfactory speed precision
• Unsatisfactory motor torque and speed response
• Motor noise

Typical Problems

The Parameter Settings Will Not Change

The Motor Does Not Rotate after You Enter a Run Command
The Motor Rotates in the Opposite Direction from the Run Command
The Motor Rotates in Only One Direction
The Motor Is Too Hot
The Correct Auto-Tuning Mode Is Not Available
The Motor Stalls during Acceleration or Accel/Decel Time Is Too Long
The Drive Frequency Reference Is Different than the Controller Frequency Reference Command
The Motor Is Not Stable When Using a PM Motor
There Is Too Much Motor Oscillation and the Rotation Is Irregular
Deceleration Takes Longer than Expected when You Enable Dynamic Braking
There Is Audible Noise from the Drive or Motor Cables when You Energize the Drive
The Ground Fault Circuit Interrupter (GFCI) Trips During Run
Motor Rotation Causes Unexpected Audible Noise from Connected Machinery
Motor Rotation Causes Oscillation or Hunting
PID Output Fault
The Starting Torque Is Not Sufficient
The Motor Rotates after You Shut Off Drive Output
The Output Frequency Is Lower Than the Frequency Reference
The Motor Is Making an Audible Noise
The Motor Will Not Restart after Power Loss
The Parameter Settings Will Not Change
Causes
The drive is operating the motor (the drive is in Drive Mode).
Parameter A1-01 = 0 [Access Level Selection = Operation Only].
Parameter H1-xx = 1B [MFDI Function Select = Programming Lockout].
YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
Symptom
Stop the drive and change to Programming Mode.
Set A1-01 = 2 [Access Level Selection = Advanced Level] or A1-01 = 3 [Expert Level].
Activate the terminals to which H1-xx = 1B is set, and then change the parameters.

2.10 Troubleshooting Without Fault Display