3.12

n: Special Adjustment

n1: Hunting Prevention

No.
Name
(Hex.)
n1-01
Hunting Prevention
Selection
(0580)
n1-02
Hunting Prevention Gain
Setting
(0581)
Expert
n1-03
Hunting Prevention Time
Constant
(0582)
Expert
n1-05
Hunting Prevent Gain in
Reverse
(0530)
Expert
n1-08
Current Detection Method
(1105)
Expert
n1-13
DC Bus Stabilization
Control
(1B59)
Expert
n1-14
DC Bus Stabilization Time
(1B5A)
Expert
n1-15
PWM Voltage Offset
Calibration
(0BF8)
Expert
n1-16
Hunting Prevention High Fc
Gain
(0BFB)
Expert
n1-17
Hunting Prevent High Fc
Filter
(0BFC)
Expert
n1-20
Voltage Calibration Duration
(1588)
Expert

n2: Auto Freq Regulator (AFR)

No.
Name
(Hex.)
n2-01
Automatic Freq Regulator
Gain
(0584)
n2-02
Automatic Freq Regulator
Time 1
(0585)
n2-03
Automatic Freq Regulator
Time 2
(0586)
YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to prevent hunting.
0 : Disabled
1 : Enabled (Normal)
2 : Enabled (High Carrier Frequency)
V/f
CL-V/f
OLV
CLV
AOLV
Sets the performance of the hunting prevention function. Usually it is not necessary to change this
parameter.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the primary delay time constant of the hunting prevention function. Usually it is not necessary to
change this parameter.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the performance of the hunting prevention function. This parameter adjusts Reverse run. Usually
it is not necessary to change this parameter.
V/f
CL-V/f
OLV
CLV
AOLV
Sets how the drive decreases the motor vibration that is caused by leakage current. Usually it is not
necessary to change this parameter.
0 : 2-Phases
1 : 3-Phases
V/f
CL-V/f
OLV
CLV
AOLV
Sets the oscillation suppression function for the DC bus voltage.
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Adjusts the responsiveness of the oscillation suppression function for the DC bus voltage. Set n1-13
= 1 [DC Bus Stabilization Control = Enabled] to enable this parameter.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the calibration method that the drive uses to decrease torque/current ripple.
0 : No Calibration
1 : One Time Calibrate at Next Start
2 : Calibrate Every Time at Start
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain for the hunting prevention function. This parameter functions best with a high carrier
frequency. Usually it is not necessary to change this parameter.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the responsiveness of the hunting prevention function. Usually it is not necessary to change this
parameter.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the calibration time at start. Usually it is not necessary to change this parameter.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain of the AFR function as a magnification value. Usually it is not necessary to change this
setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time constant that sets the rate of change for the AFR function. Usually it is not necessary to
change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time constant that sets the speed difference of the AFR function. Use this parameter for
speed searches or regeneration. Usually it is not necessary to change this setting.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM

3.12 n: Special Adjustment

Default
(Range)
Determined by o2-04
(0 to 2)
1.00
(0.00 - 2.50)
Determined by o2-04
(0 - 500 ms)
0.00
(0.00 - 2.50)
0
(0, 1)
0
(0, 1)
100.0 ms
(50.0 - 500.0 ms)
Determined by A1-02
(0 - 2)
Determined by o2-04
(0.00 - 2.50)
500 ms
(0 - 1000 ms)
50 ms
(10 - 500 ms)
Default
(Range)
1.00
(0.00 - 10.00)
50 ms
(0 - 2000 ms)
750 ms
(0 - 2000 ms)
3
235