N3: High Slip/Overexcite Braking; N4: Adv Open Loop Vector Tune - YASKAWA GA800 Maintenance & Troubleshooting

Ac drive for industrial applications, three-phase 200/400 v class: 1 to 150/600 hp, 6-phase/12-pulse 400 v class: 75 to 600 hp
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

3.12 n: Special Adjustment

n3: High Slip/Overexcite Braking

No.
Name
(Hex.)
n3-01
HSB Deceleration
Frequency Width
(0588)
Expert
n3-02
HSB Current Limit Level
(0589)
Expert
n3-03
HSB Dwell Time at Stop
(058A)
Expert
n3-04
HSB Overload Time
(058B)
Expert
n3-13
OverexcitationBraking
(OEB) Gain
(0531)
n3-14
OEB High Frequency
Injection
(0532)
Expert
n3-21
HSB Current Suppression
Level
(0579)
n3-23
Overexcitation Braking
Operation
(057B)

n4: Adv Open Loop Vector Tune

No.
Name
(Hex.)
n4-60
Motoring Low Speed Comp
Gain
(1B80)
n4-61
Low Speed Comp Frequency
Level
(1B81)
n4-62
Regen Low Speed Comp
Gain
(1B82)
n4-63
Speed
EstimateResponse@High
(1B83)
Freq
n4-64
Speed Estimate
Response@Low Freq
(1B84)
n4-65
Flux Estimate
Response@High Freq
(1B85)
236
V/f
CL-V/f
OLV
CLV
AOLV
Sets the amount by which the output frequency is to be lowered during high-slip braking, as a
percentage of E1-04 [Maximum Output Frequency], which represents the 100% value.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the maximum current output during high-slip braking as a percentage, where E2-01 [Motor
Rated Current (FLA)] is 100%. Also set the current suppression to prevent exceeding drive overload
tolerance.
Note:
The upper limit to the setting range changes when the setting for C6-01 [Normal / Heavy Duty
Selection] changes.
• 150% when C6-01 = 0 [Heavy Duty Rating]
• 110% when C6-01 = 1 [Normal Duty Rating]
V/f
CL-V/f
OLV
CLV
AOLV
Sets the dwell time, a length of time when high-slip braking is ending and during which the motor
speed decreases and runs at a stable speed. For a set length of time, the drive will hold the actual
output frequency at the minimum output frequency set in E1-09.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time used to detect oL7 [High Slip Braking Overload], which occurs when the output
frequency does not change during high-slip braking. Usually it is not necessary to change this
parameter.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain value that the drive multiplies by the V/f pattern output value during overexcitation
deceleration to calculate the overexcitation level.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function that injects harmonic signals during overexcitation deceleration.
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets the upper limit of the current that is suppressed at the time of overexcitation deceleration as a
percentage of the drive rated current.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the direction of motor rotation where the drive will enable overexcitation.
0 : Disabled
1 : Enabled Only when Rotating FWD
2 : Enabled Only when Rotating REV
V/f
CL-V/f
OLV
CLV
AOLV
Sets a compensation gain to improve the control qualities for motoring loads in the low speed range.
V/f
CL-V/f
OLV
CLV
AOLV
Sets a frequency at which the settings n4-60 [Motoring Low Speed Comp Gain] and n4-62 [Regen
Low Speed Comp Gain] are enabled. When the output frequency < n4-61, the drive adjusts the torque
to agree with the settings for n4-60 and n4-62. Usually it is not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets a compensation gain to improve the control qualities for regenerative loads in the low speed
range.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the responsiveness of the speed estimation in high speed ranges, where the output frequency is ≥
n4-67 [Estimate Gain Switchover Freq].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the responsiveness of the speed estimation in low speed ranges, where 0 ≤ the output frequency,
which is < n4-67 [Estimate Gain Switchover Freq].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the responsiveness of the magnetic flux estimation in high speed ranges, where the output
frequency is ≥ n4-67 [Estimate Gain Switchover Freq]. Usually it is not necessary to change this
setting.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
Default
(Range)
5%
(1 - 20%)
Determined by C6-01 and
L8-38
(0 - 150%)
1.0 s
(0.0 - 10.0 s)
40 s
(30 - 1200 s)
1.10
(1.00 - 1.40)
0
(0, 1)
100%
(0 - 150%)
0
(0 - 2)
Default
(Range)
100.0%
(50.0 - 200.0%)
6.00 Hz
(0.50 - 12.00 Hz)
100.0 %
(50.0 - 500.0%)
60.0
(0.1 - 300.0)
60.0
(0.1 - 300.0)
1.00
(0.50 - 3.00)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents