D2: Reference Limits - YASKAWA GA800 Maintenance & Troubleshooting

Ac drive for industrial applications, three-phase 200/400 v class: 1 to 150/600 hp, 6-phase/12-pulse 400 v class: 75 to 600 hp
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

3.7 d: Reference Settings
No.
Name
(Hex.)
d1-12
Reference 12
(028D)
RUN
d1-13
Reference 13
(028E)
RUN
d1-14
Reference 14
(028F)
RUN
d1-15
Reference 15
(0290)
RUN
d1-16
Reference 16
(0291)
RUN
d1-17
Jog Reference
(0292)
RUN

d2: Reference Limits

No.
Name
(Hex.)
d2-01
Frequency Reference Upper
Limit
(0289)
d2-02
Frequency Reference Lower
Limit
(028A)
d2-03
Analog Frequency Ref
Lower Limit
(0293)
174
V/f
CL-V/f
OLV
CLV
AOLV
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
Note:
When A1-02 = 6, 7 [Control Method Selection = AOLV/PM, CLV/PM], the drive changes o1-03
= 1 [0.01% (100% = E1-04)].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
Note:
When A1-02 = 6, 7 [Control Method Selection = AOLV/PM, CLV/PM], the drive changes o1-03
= 1 [0.01% (100% = E1-04)].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
Note:
When A1-02 = 6, 7 [Control Method Selection = AOLV/PM, CLV/PM], the drive changes o1-03
= 1 [0.01% (100% = E1-04)].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
Note:
When A1-02 = 6, 7 [Control Method Selection = AOLV/PM, CLV/PM], the drive changes o1-03
= 1 [0.01% (100% = E1-04)].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
Note:
When A1-02 = 6, 7 [Control Method Selection = AOLV/PM, CLV/PM], the drive changes o1-03
= 1 [0.01% (100% = E1-04)].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the Jog frequency reference in the units from o1-03 [Frequency Display Unit Selection]. Set H1-
xx = 6 [MFDI Function Select = Jog Reference Selection] to use the Jog frequency reference.
Note:
When A1-02 = 6, 7 [Control Method Selection = AOLV/PM, CLV/PM], the drive sets o1-03 = 1
[0.01% (100% = E1-04)].
V/f
CL-V/f
OLV
CLV
AOLV
Sets maximum limit for all frequency references. The maximum output frequency is 100%.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output
frequency.
• A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Motor Max Revolutions]
V/f
CL-V/f
OLV
CLV
AOLV
Sets minimum limit for all frequency references. The maximum output frequency is 100%.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output
frequency.
• A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Motor Max Revolutions]
V/f
CL-V/f
OLV
CLV
AOLV
Sets the lower limit for the master frequency reference (the first frequency of the multi-step speed
reference) as a percentage. The maximum output frequency is 100%.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output
frequency.
• A1-02 ≠ 8: E1-04 [Maximum Output Frequency]
• A1-02 = 8: E9-02 [Maximum Speed]
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
YASKAWA TOEPYAIGA8001B GA800 Drive Maintenance & Troubleshooting
Default
(Range)
0.00 Hz
(0.00 - 590.00 Hz)
0.00 Hz
(0.00 - 590.00 Hz)
0.00 Hz
(0.00 - 590.00 Hz)
0.00 Hz
(0.00 - 590.00 Hz)
0.00 Hz
(0.00 - 590.00 Hz)
6.00 Hz
(0.00 - 590.00 Hz)
Default
(Range)
100.0%
(0.0 - 110.0%)
0.0%
(0.0 - 110.0%)
0.0%
(0.0 - 110.0%)

Hide quick links: