Physical installation
............................................................................................................................................................................................................................................................

Power cable installation

Description
This section provides instructions on installing the power cabling for the Alcatel-Lucent
1850 TSS-5 shelf.
Each power feeder (A and B) requires a single power feed from the battery distribution
fuse board (BDFB), or the battery distribution circuit breaker bay (BDCBB) to the
Alcatel-Lucent 1850 TSS-5 shelf.
If the Alcatel-Lucent 1850 TSS-5 is powered through only one power feed, the system will
report a minor alarm. To suppress the alarm, use two jumpers, one jumper between the -
VA and -VB and the second jumper between +VA and +VB. The gauge of both jumpers
should be the same as the gauge being brought in from either the Battery Plant (#12AWG
to #20AWG).
Table 2-3, "Power cable assembly" (p. 2-13)
-48V connection" (p.
respectively
Table 2-3 Power cable assembly
Description
DC Power cable 12 AWG 4 conductors
from power block to DC power source, both ends un-
terminated.
Procedure
Proceed as follows:
........................................................................................................................................................................................................................
1
Verify the power source is off.
........................................................................................................................................................................................................................
2
Connect the A and B power cables to the A and B connector pins of the terminal block
located on the top right. Use a torque screwdriver set to 0.5 nm (4.4 lb-in) to tighten. See
Figure 2-8, "Power terminal block" (p.
Note:
strip length for connection to the terminal block. Use the guide located on the shelf
labeling for accurate lengths.
............................................................................................................................................................................................................................................................
365-372-403R5.1
Issue 1 November 2008
2-14)list the available power cable assembly and power connections,
Power cables must be between 12 AWG and 20 AWG and have an 9-mm wire
and
Table 2-4, "Power cable color coding for
Cable
Assembly #
848946687
2-11).
Power cable installation
Cable
Length (feet)
30
2 - 1 3