Power Cable Color Coding For -48V Connection; Power Cable Color Coding For +24V Connection - Alcatel-Lucent 1850 Installation And System Turn-Up Manual

Transport service switch (tss-5) | release 5.1
Hide thumbs Also See for 1850:
Table of Contents

Advertisement

Physical installation
............................................................................................................................................................................................................................................................
12AWG wire allows for the greatest distance between a power source(BDFB) and the
Alcatel-Lucent 1850 TSS-5 shelf.
Table 2-4 Power cable color coding for -48V connection
Note:
GND and +VB and GND. The dc terminal block can accommodate wire sizes from 12
to 20 AWG, however, if jumpering between positions, for grounding, the maximum
wire size that allows 2-wires into same hole is 16AWG.
Table 2-5 Power cable color coding for +24V connection
Note:
GND and -VB and GND. The dc terminal block can accommodate wire sizes from 12
to 20 AWG, however, if jumpering between positions, for grounding, the maximum
wire size that allows 2-wires into same hole is 16 AWG.
........................................................................................................................................................................................................................
1
Route the power cables toward the power source (e.g., BDCBB, BDFB etc.)
Note:
............................................................................................................................................................................................................................................................
2 - 1 4
BAT A
BAT B
For 48Vgrounding when using -48V, add a 16 AWG strap between +VA and
BAT A
BAT B
For 24V grounding when using +24V add a 16 AWG strap between -VA and
The Alcatel-Lucent 1850 TSS-5 is powered by either +24V DC or -48 V DC.
CAUTION
If using BBCBB or BDFB, verify that the BDCBB breakers are off or that the
BDFB fuses are not installed.
Color Coding
Connection
Red
-VA
Red/Black
+VA
Blue
-VB
Blue/Black
+VB
Color Coding
Connection
Red
+VA
Red/Black
-VA
Blue
+VB
Blue/Black
-VB
Power cable installation
365-372-403R5.1
Issue 1 November 2008

Advertisement

Table of Contents
loading