Agilent Technologies 16522A User Manual page 40

200-m vectors/s pattern generator
Table of Contents

Advertisement

Agilent Technologies 16522A Reference
The Sequence Menu
Step
Use the Step field to step through your vector sequence to debug a critical
set of vectors following a break instruction in the program sequence.
Stepping will begin at the vector following the break instruction or the
Output First State item can be pressed which will place the first vector of the
sequence on the outputs. Stepping will then begin on the second vector of
the sequence. When the last vector of the main sequence is encountered
while stepping, the next step command places the first vector of the main
sequence on the outputs.
When stepping through a sequence, breaks are ignored while valid branch
and wait conditions are executed.
The Step Count field lets you set the number of steps to be executed, up to
100,000. The Output First State field reloads the hardware if necessary and
places the first vector of the sequence on the outputs. The Resume field
closes the Step pop-up menu and restarts the hardware without changing the
previous run mode. Execution resumes from the point at which the
sequence was stopped.
Delete
The Delete field lets you delete sequence lines. The From and To fields in
the Delete pop-up menu lets you select line numbers with either the knob or
another pop-up menu that appears when the From and To fields are touched
twice.
2–8

Advertisement

Table of Contents
loading

Table of Contents