7.3
Positioning the boiler on a sub-
structure or on foundations
USER NOTE
As accessory Buderus offers a boiler plinth
designed to reduce body resonance.
You can cast a concrete plinth if the optional boiler plinth
is not used. When casting the plinth, you must
incorporate a steel angle with the dimensions
100 x 50 x 8 mm or a steel strip with the dimensions
100 x 5 mm (
Fig. 7 and the following table), to ensure
the boiler sections will slide into position during
installation.
USER NOTE
When casting the foundation, note the
side to which the burner will be pivoted
(burner door hinged on the r.h. or l.h.
side, Fig. 6, page 16).
It is advantageous to position the boiler on a plinth
50 - 80 cm high (Fig. 7, [1]). The support surface must
be perfectly flat and level. The front edge of the boiler
should be flush with the edge of the foundation.
Number of
L
(foundation)
1
boiler sections
7
8
9
10
11
12
Logano GE515 - We reserve the right to make any changes due to technical modifications.
L
(length of
2
steel section)
in mm
in mm
1 360
1 190
1 530
1 360
1 700
1 530
1 870
1 700
2 040
1 870
2 210
2 040
1
Fig. 7
Foundation dimensions in mm
Boiler positioning
7
17