Specification - Buderus Logano GE515 Installation And Maintenance Instructions Manual

Oil- and gas-fired boilers
Hide thumbs Also See for Logano GE515:
Table of Contents

Advertisement

4

Specification

4
Specification
The specification provides information about the Logano
GE515 output profile.
Fig. 3
Logano GE515 specification (dimensions in mm)
1
Connection flange reduced in accordance with order to DN 100, DN 80 or DN 65.
2
Fill the boiler and the system via a separate connector in the return pipe.
3
The drain cock (EL) is only suitable for draining the system, not for filling.
EL
=
Drain connection (Rp ¾")
L
=
Length of boiler block
K
L
=
Overall boiler length
RK
=
Boiler return connection
VK
=
Boiler flow connection
Boiler size
Boiler sections
Rated output
Combustion output
Overall boiler length (L)
Length of boiler block
(L
)
K
Boiler section transport
dimension
Boiler block handling
Length of combustion
chamber
Diameter of combustion
chamber
Depth of burner door
1
Net weight
Boiler water content
Gas capacity
1
Weight incl. packaging approx. 6–8 % higher.
10
240
Number
7
kW
201–240
kW
215.6–259.7
257.8–319.0
mm
1 580
mm
1 360
mm
mm
mm
1 165
mm
mm
kg
1270
l
258
l
421
Logano GE515 - We reserve the right to make any changes due to technical modifications.
Logano GE515
295
350
8
9
241–295
296–350
316.6–377.1
1 750
1 920
1 530
1 700
width 835 / height 1315 / depth 170
width 835 / height 1315 / length L
1 335
1 505
515
142
1430
1590
294
330
487
551
400
455
10
11
351–400
401–455
374.6–429.6
428.4–489.2
2 090
2 260
1 870
2 040
K
1 675
1 845
1753
1900
366
402
616
681
510
12
456–510
488.2–547.8
2 430
2 210
2 015
2060
438
745

Hide quick links: