System inspection and maintenance
Remove the hot gas baffle plates by pulling them
forward out of the hot gas flues (Fig. 72, [1] to [4]).
USER NOTE
The boiler size 510 with 12 boiler sections
is not equipped with hot gas baffle plates.
Hot gas baffle plates are used in boiler
sizes 240–455 with 7–11 boiler sections
(
chapter 8.8.5 "Insert the hot gas baffle
plates", page 33).
You will find an illustration of the various types of
brushes offered by Buderus (accessory) in Fig. 73.
Clean the hot gas flues with cleaning brushes 1 and
2 from the front to the back (Fig. 74, [1] and [3]).
Clean the combustion chamber with cleaning
brush 3.
Clean the remainder of the combustion chamber
(Fig. 74, [2]) with cleaning brush 2.
58
Logano GE515 - We reserve the right to make any changes due to technical modifications.
4
3
2
1
Fig. 72 Remove the hot gas baffle plates
Fig. 73 Cleaning brushes
3
2
1
1
Fig. 74 Clean the hot gas flues