How to Program
Parameter Set-up
The adjustable frequency drive can be used for practically all assignments, thus offering a significant number
of parameters. The series offers a choice between two programming modes - the Quick Menu mode and the
Main Menu mode.
The latter provides access to all parameters. The former takes the user through a few parameters making it
possible to program the majority of TR200 applications.
Regardless of the mode of programming, you can change a parameter both in quick menu mode and in main
menu mode.

Quick Menu mode

Parameter data
The keypad provides access to all parameters listed under the quick menus. To set parameters using the [Quick
Menu] button - enter or change parameter data or settings in accordance with the following procedure:
1.
Press Quick Menu button
2.
Use the [ ] and [ ] buttons to find the parameter you want to change
3.
Press [OK]
4.
Use [ ] and [ ] buttons to select the correct parameter setting
5.
Press [OK]
6.
To move to a different digit within a parameter setting, use the [ ] and [ ] buttons
7.
Highlighted area indicates digit selected for change
8.
Press [Cancel] button to disregard change, or press [OK] to accept change and enter the new setting
Example of changing parameter data
Assume parameter 22-60 is set to [Off]. However, you want to monitor the fan belt condition - non-broken or
broken - according to the following procedure:
1.
Press Quick Menu key
2.
Choose Function Set-ups with the [ ] button
3.
Press [OK]
4.
Choose Application Settings with the [ ] button
5.
Press [OK]
6.
Press [OK] again for Fan Functions
7.
Choose Broken Belt Function by pressing [OK]
8.
With [ ] button, choose [2] Trip
The adjustable frequency drive will now trip if a broken fan belt is detected.
Select [My Personal Menu] to display personal parameters:
Select [My Personal Menu] to display only the parameters, which have been pre-selected and programmed as
personal parameters. For example, you may have pre-programmed personal parameters to be in My Personal
Menu during factory commissioning to make on-site commissioning/fine tuning simpler. These parameters are
selected in par.0-25
My Personal
3-8
Menu. Up to 20 different parameters can be programmed in this menu.
TR200 Programming Guide