Parameter Description
1-52 Min Speed Normal Magnetizing [Hz]
Range:
Applica-
[Application dependant]
tion de-
pend-
ent*
1-6* Load Depend. Setting
Parameters for adjusting the load-dependent motor settings.
1-60 Low Speed Load Compensation
Range:
100 %* [0 - 300 %]
1-61 High Speed Load Compensation
Range:
100 %* [0 - 300 %]
4-28
Function:
Function:
Enter the % value to compensate voltage in relation to load while the
motor is running at low speed, and obtain the optimum U/f characteristic.
The motor size determines the frequency range within which this pa-
rameter is active.
Motor size
0.3–10 hp [0.25–7.5 kW]
15–60 hp [11–45 kW]
75–750 hp [55 kW–550 kW]
Function:
Enter the % value to compensate voltage in relation to load while the
motor is running at high speed, and obtain the optimum U/f character-
istic. The motor size determines the frequency range within which this
parameter is active.
Motor size
0.3–10 hp [0.25–7.5 kW]
15–60 hp [11–45 kW]
75–750 hp [55 kW–550 kW]
Change-over
< 10 Hz
< 5 Hz
< 3–4 Hz
Change-over
> 10 Hz
< 5 Hz
< 3–4 Hz
TR200 Programming Guide