13-41 Logic Rule Operator 1
Array [6]
Option:
[0] *
DISABLED
[1]
AND
[2]
OR
[3]
AND NOT
[4]
OR NOT
[5]
NOT AND
[6]
NOT OR
[7]
NOT AND NOT
[8]
NOT OR NOT
13-42 Logic Rule Boolean 2
Array [6]
Option:
[0] *
FALSE
[1]
TRUE
[2]
Running
[3]
In range
[4]
On reference
[5]
Torque limit
[6]
Current limit
[7]
Out of current range
[8]
Below I low
[9]
Above I high
[10]
Out of speed range
[11]
Below speed low
[12]
Above speed high
[13]
Out of feedb. range
[14]
Below feedb. low
[15]
Above feedb. high
[16]
Thermal warning
TR200 Programming Guide
Function:
Select the first logical operator to use on the Boolean inputs from par.
13-40
Logic Rule Boolean 1
[13 -XX] signifies the Boolean input of par. 13-*.
Ignores par.13-42
Logic Rule Boolean
2, and par.13-44
Logic Rule Boolean
Evaluates the expression [13-40] AND [13-42].
evaluates the expression [13-40] OR[13-42].
evaluates the expression [13-40] AND NOT [13-42].
evaluates the expression [13-40] OR NOT [13-42].
evaluates the expression NOT [13-40] AND [13-42].
evaluates the expression NOT [13-40] OR [13-42].
evaluates the expression NOT [13-40] AND NOT [13-42].
evaluates the expression NOT [13-40] OR NOT [13-42].
Function:
Select the second Boolean (TRUE or FALSE) input for the selected logic
rule.
See par.13-40
Logic Rule Boolean 1
and their functions.
Parameter Description
and par.13-42
Logic Rule Boolean
2, par.13-43
Logic Rule Operator
3.
for further descriptions of choices