Trane TR200 Programming Manual page 125

Hide thumbs Also See for TR200:
Table of Contents

Advertisement

Parameter Description
6-4* Analog Input 4 MCB 101
Parameter group for configuring the scale and limits for analog input 4 (X30/12) placed on option module MCB
101.
6-40 Terminal X30/12 Low Voltage
Range:
0.07 V* [Application dependant]
6-41 Terminal X30/12 High Voltage
Range:
10.00 V* [Application dependant]
6-44 Term. X30/12 Low Ref./Feedb. Value
Range:
0.000 N/
[-999999.999 - 999999.999
A*
N/A]
6-45 Term. X30/12 High Ref./Feedb. Value
Range:
100.000
[-999999.999 - 999999.999
N/A*
N/A]
6-46 Term. X30/12 Filter Time Constant
Range:
0.001 s* [0.001 - 10.000 s]
6-47 Term. X30/12 Live Zero
Option:
[0] *
Disabled
[1] *
Enabled
4-88
Function:
Sets the analog input scaling value to correspond to the low reference/
feedback value set in par.6-44
Function:
Sets the analog input scaling value to correspond to the high reference/
feedback value set in par.6-45
Function:
Sets the analog output scaling value to correspond to the low voltage
value set in par.6-40
Terminal X30/12 Low
Function:
Sets the analog input scaling value to correspond to the high voltage
value set in par.6-41
Terminal X30/12 High
Function:
A 1 st order digital low pass filter time constant for suppressing electrical
noise on terminal X30/12.
par.6-46
Term. X30/12 Filter Time Constant
motor is running.
Function:
This parameter makes it possible to disable Live Zero monitoring. For
example, this may be used if the analog outputs are used as part of a
decentral I/O system (e.g., when not part of any adjustable frequency
drive-related control functions, but feeding a building management sys-
tem with data).
Term. X30/12 Low Ref./Feedb.
Term. X30/12 High Ref./Feedb.
Voltage.
Voltage.
cannot be changed while the
TR200 Programming Guide
Value.
Value.