Parameter Description
22-76 Interval between Starts
Range:
Applica-
[Application dependant]
tion de-
pend-
ent*
22-77 Minimum Run Time
Range:
0 s*
[Application dependant]
NOTE: Does not work in cascade mode.

Main Menu - Time-based Functions - TR200 - Group 23

23-0* Timed Actions
Timed Actions
Use
for actions needing to be performed on a daily or weekly basis, e.g., different references for
working hours / non-working hours. Up to 10 Timed Actions can be programmed in the adjustable frequency
drive. The Timed Action number is selected from the list when entering parameter group 23-0* from the
keypad. par.23-00
ON Time
action is divided into an ON time and an OFF time, in which two different actions may be performed.
NOTE
The clock (parameter group 0-7*) must be correctly programmed for timed actions to function correctly.
NOTE
When mounting an Analog I/O MCB 115 option card, a battery backup of the date and time is included.
23-00 ON Time
Array [10]
Range:
Applica-
[Application dependant]
tion de-
pend-
ent*
4-192
Function:
Function:
Sets the time desired as minimum run time after a normal start command
(Start/Jog/Freeze). Any normal stop command will be disregarded until
the set time has expired. The timer will start counting following a normal
start command (Start/Jog/Freeze).
The timer will be overridden by a Coast (Inverse) or an External Interlock
command.
– par.23-04
Occurrence
then refer to the selected Timed Action number. Each timed
Function:
TR200 Programming Guide