Trane TR200 Programming Manual page 241

Hide thumbs Also See for TR200:
Table of Contents

Advertisement

Parameter Description
Once a second, the value of the operating variable selected is registered. If a value has been registered to equal
13%, the counter "10%–<20%" will be updated with the value "1". If the value stays at 13% for 10s, then "10"
will be added to the counter value.
The contents of counters can be displayed as bars on keypad. Select
Bin / Trending Timed Bin / Trending Comparison
NOTE
The counters starts counting whenever the adjustable frequency drive is powered up. The power cycle will shortly after
a reset zero the counters. EEProm data are updated once per hour.
23-60 Trend Variable
Option:
[0] *
Power [kW]
[1]
Current [A]
[2]
Frequency [Hz]
[3]
Motor Speed [RPM]
4-204
.
Function:
Select the desired operating variable to be monitored for trending.
Power yielded to the motor. Reference for the relative value is the rated
motor power programmed in par.1-20
1-21
Motor Power
[HP]. Actual value can be read in par.16-10
[kW]
or par.16-11
Power
[hp].
Output current to the motor. Reference for the relative value is the rated
motor current programmed in par.1-24
be read in par.16-14
Motor
Output frequency to the motor. Reference for the relative value is the
maximum output frequency programmed in par.4-14
Limit
[Hz]. Actual value can be read in par.16-13 Frequency.
Speed of the motor. Reference for relative value is the maximum motor
speed programmed in par.4-13
Quick Menu
Loggings
Trending Continued
>
:
Motor Power [kW]
Motor
Current. Actual value can
Current.
Motor Speed High
Motor Speed High Limit
TR200 Programming Guide
or par.
Power
[RPM].