Data Readouts - Trane TR200 Programming Manual

Hide thumbs Also See for TR200:
Table of Contents

Advertisement

Parameter Lists

16-** Data Readouts

Par.
Parameter description
No. #
16-0* General Status
16-00
Control Word
16-01
Reference [Unit]
16-02
Reference %
16-03
Status Word
16-05
Main Actual Value [%]
16-09
Custom Readout
16-1* Motor Status
16-10
Power [kW]
16-11
Power [hp]
16-12
Motor voltage
16-13
Frequency
16-14
Motor Current
16-15
Frequency [%]
16-16
Torque [Nm]
16-17
Speed [RPM]
16-18
Motor Thermal
16-22
Torque [%]
16-26
Power Filtered [kW]
16-27
Power Filtered [hp]
16-3* Drive Status
16-30
DC Link Voltage
16-32
Brake Energy /s
16-33
Brake Energy /2 min
16-34
Heatsink Temp.
16-35
Inverter Thermal
16-36
Inv. Nom. Current
16-37
Inv. Max. Current
16-38
SL Controller State
16-39
Control Card Temp.
16-40
Logging Buffer Full
16-49
Current Fault Source
16-5* Ref. & Feedb.
16-50
External Reference
16-52
Feedback [Unit]
16-53
Digi Pot Reference
16-54
Feedback 1 [Unit]
16-55
Feedback 2 [Unit]
16-56
Feedback 3 [Unit]
16-58
PID Output [%]
16-6* Inputs & Outputs
16-60
Digital Input
16-61
Terminal 53 Switch Setting
16-62
Analog Input 53
16-63
Terminal 54 Switch Setting
16-64
Analog Input 54
16-65
Analog Output 42 [mA]
16-66
Digital Output [bin]
16-67
Pulse Input #29 [Hz]
16-68
Pulse Input #33 [Hz]
16-69
Pulse Output #27 [Hz]
16-70
Pulse Output #29 [Hz]
16-71
Relay Output [bin]
16-72
Counter A
16-73
Counter B
16-75
Analog In X30/11
16-76
Analog In X30/12
16-77
Analog Out X30/8 [mA]
16-8* Fieldbus & FC Port
16-80
Fieldbus CTW 1
16-82
Fieldbus REF 1
16-84
Comm. Option Status
16-85
FC Port CTW 1
16-86
FC Port REF 1
16-9* Diagnosis Readouts
16-90
Alarm Word
16-91
Alarm word 2
16-92
Warning Word
16-93
Warning word 2
16-94
Ext. Status Word
16-95
Ext. Status Word 2
16-96
Maintenance Word
6-12
Default value
4-set-up
0 N/A
All set-ups
0.000 ReferenceFeedbackUnit
All set-ups
0.0 %
All set-ups
0 N/A
All set-ups
0.00 %
All set-ups
0.00 CustomReadoutUnit
All set-ups
0.00 kW
All set-ups
0.00 hp
All set-ups
0.0 V
All set-ups
0.0 Hz
All set-ups
0.00 A
All set-ups
0.00 %
All set-ups
0.0 Nm
All set-ups
0 RPM
All set-ups
0 %
All set-ups
0 %
All set-ups
0.000 kW
All set-ups
0.000 hp
All set-ups
0 V
All set-ups
0.000 kW
All set-ups
0.000 kW
All set-ups
0 °C
All set-ups
0 %
All set-ups
ExpressionLimit
All set-ups
ExpressionLimit
All set-ups
0 N/A
All set-ups
0 °C
All set-ups
[0] No
All set-ups
0 N/A
All set-ups
0.0 N/A
All set-ups
0.000 ProcessCtrlUnit
All set-ups
0.00 N/A
All set-ups
0.000 ProcessCtrlUnit
All set-ups
0.000 ProcessCtrlUnit
All set-ups
0.000 ProcessCtrlUnit
All set-ups
0.0 %
All set-ups
0 N/A
All set-ups
[0] Current
All set-ups
0.000 N/A
All set-ups
[0] Current
All set-ups
0.000 N/A
All set-ups
0.000 N/A
All set-ups
0 N/A
All set-ups
0 N/A
All set-ups
0 N/A
All set-ups
0 N/A
All set-ups
0 N/A
All set-ups
0 N/A
All set-ups
0 N/A
All set-ups
0 N/A
All set-ups
0.000 N/A
All set-ups
0.000 N/A
All set-ups
0.000 N/A
All set-ups
0 N/A
All set-ups
0 N/A
All set-ups
0 N/A
All set-ups
0 N/A
All set-ups
0 N/A
All set-ups
0 N/A
All set-ups
0 N/A
All set-ups
0 N/A
All set-ups
0 N/A
All set-ups
0 N/A
All set-ups
0 N/A
All set-ups
0 N/A
All set-ups
Change dur-
Conver-
Type
ing opera-
sion index
tion
FALSE
0
V2
FALSE
-3
Int32
FALSE
-1
Int16
FALSE
0
V2
FALSE
-2
N2
FALSE
-2
Int32
FALSE
1
Int32
FALSE
-2
Int32
FALSE
-1
Uint16
FALSE
-1
Uint16
FALSE
-2
Int32
FALSE
-2
N2
FALSE
-1
Int32
FALSE
67
Int32
FALSE
0
Uint8
FALSE
0
Int16
FALSE
0
Int32
FALSE
-3
Int32
FALSE
0
Uint16
FALSE
0
Uint32
FALSE
0
Uint32
FALSE
100
Uint8
FALSE
0
Uint8
FALSE
-2
Uint32
FALSE
-2
Uint32
FALSE
0
Uint8
FALSE
100
Uint8
TRUE
-
Uint8
TRUE
0
Uint8
FALSE
-1
Int16
FALSE
-3
Int32
FALSE
-2
Int16
FALSE
-3
Int32
FALSE
-3
Int32
FALSE
-3
Int32
TRUE
-1
Int16
FALSE
0
Uint16
FALSE
-
Uint8
FALSE
-3
Int32
FALSE
-
Uint8
FALSE
-3
Int32
FALSE
-3
Int16
FALSE
0
Int16
FALSE
0
Int32
FALSE
0
Int32
FALSE
0
Int32
FALSE
0
Int32
FALSE
0
Int16
TRUE
0
Int32
TRUE
0
Int32
FALSE
-3
Int32
FALSE
-3
Int32
FALSE
-3
Int16
FALSE
0
V2
FALSE
0
N2
FALSE
0
V2
FALSE
0
V2
FALSE
0
N2
FALSE
0
Uint32
FALSE
0
Uint32
FALSE
0
Uint32
FALSE
0
Uint32
FALSE
0
Uint32
FALSE
0
Uint32
FALSE
0
Uint32
TR200 Programming Guide

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents