[3]
Drive ready / remote con-
trol
[4]
Stand-by / no warning
[5]
Running
[6]
Running / no warning
[8]
Run on reference / no
warning
[9]
Alarm
[10]
Alarm or warning
[11]
At torque limit
[12]
Out of current range
[13]
Below current, low
[14]
Above current, high
[15]
Out of speed range
[16]
Below speed, low
[17]
Above speed, high
[18]
Out of feedback range
[19]
Below feedback low
[20]
Above feedback high
[21]
Thermal warning
[25]
Reverse
[26]
Bus OK
[27]
Torque limit and stop
[28]
Brake, no warning
[29]
Brake ready, no fault
[30]
Brake fault (IGBT)
[35]
External Interlock
[40]
Out of ref range
[41]
Below reference low
[42]
Above reference high
TR200 Programming Guide
The adjustable frequency drive is ready for operation and is in Auto On
mode.
The adjustable frequency drive is ready for operation. No start or stop
command is been given (start/disable). There are no warnings.
The motor is running.
The output speed is higher than the speed set in par.1-81
Function at Stop
[RPM]. The motor is running and there are no warnings.
The motor runs at reference speed.
An alarm activates the output. There are no warnings.
An alarm or a warning activates the output.
The torque limit set in par.4-16
been exceeded.
The motor current is outside the range set in par.4-18
The motor current is lower than set in par.4-50
The motor current is higher than set in par.4-51
The output speed is outside the range set in par.4-52
Low
and par.4-53
Warning Speed
The output speed is lower than the setting in par.4-52
Low.
The output speed is higher than the setting in par.4-53
High.
The feedback is outside the range set in par.4-56
Low
and par.4-57
Warning Feedback
The feedback is below the limit set in par.4-56
The feedback is above the limit set in par.4-57
The thermal warning turns on when the temperature exceeds the limit
in the motor, the adjustable frequency drive, the brake resistor, or the
thermistor.
Reversing. Logic '1' =
relay activated, 24 V DC when CW rotation of the
motor. Logic '0' = relay not activated, no signal, when CCW rotation of
the motor.
Active communication (no timeout) via the serial communication port.
Use in performing a coasting stop and in torque limit condition. If the
adjustable frequency drive has received a stop signal and is at the torque
limit, the signal is Logic '0'.
The brake is active and there are no warnings.
The brake is ready for operation and there are no faults.
The output is Logic '1' when the brake IGBT is short-circuited. Use this
function to protect the adjustable frequency drive if there is a fault on the
brake modules. Use the output/relay to cut out the AC line voltage from
the adjustable frequency drive.
External Interlock function has been activated via one of the digital in-
puts.
Parameter Description
Torque Limit Motor Mode
or par. 1-17 has
Current
Warning Current
Warning Current
Warning Speed
High.
Warning Speed
Warning Speed
Warning Feedback
High.
Warning Feedback
Warning Feedback
Min Speed for
Limit.
Low.
High.
Low.
High.
4-67