Main Menu - Analog In/Out - Group 6

6-** Analog In/Out
Parameter group for configuring the analog input and output.
6-0* Analog I/O Mode
Parameter group for setting up the analog I/O configuration.
The adjustable frequency drive is equipped with 2 analog inputs: Terminal 53 and 54. The analog inputs can
freely be allocated to either voltage (0–10 V) or current input (0/4–20 mA)
NOTE
Thermistors may be connected to either an analog or a digital input.
6-00 Live Zero Timeout Time
Range:
10 s*
[1 - 99 s]
6-01 Live Zero Timeout Function
Option:
[0] *
Off
[1]
Freeze output
[2]
Stop
[3]
Jogging
TR200 Programming Guide
Function:
Enter the Live Zero Timeout time period. Live Zero Timeout Time is active
for analog inputs, i.e., terminal 53 or terminal 54, used as reference or
feedback sources. If the reference signal value associated with the se-
lected current input falls below 50% of the value set in par.6-10
53 Low
Voltage, par.6-12
Terminal 53 Low
Low Voltage
or par.6-22
Terminal 54 Low Current
than the time set in par.6-00
ted in par.6-01
Live Zero Timeout Function
Function:
Select the timeout function. The function set in par.6-01
out Function
will be activated if the input signal on terminal 53 or 54 is
below 50% of the value in par.6-10
6-12
Terminal 53 Low
Current, par.6-20
6-22
Terminal 54 Low Current
Zero Timeout
Time. If several timeouts occur simultaneously, the ad-
justable frequency drive prioritizes the timeout functions as follows:
1.
par.6-01
Live Zero Timeout Function
2.
par.8-04
Control Timeout Function
The output frequency of the adjustable frequency drive can be:
[1] frozen at the present value
[2] overruled to stop
[3] overruled to jog speed
[4] overruled to max. speed
[5] overruled to stop with subsequent trip
Parameter Description
Current, par.6-20
for a time period longer
Live Zero Timeout
Time, the function selec-
will be activated.
Terminal 53 Low
Voltage, par.
Terminal 54 Low Voltage
for a time period defined in par.6-00
Terminal
Terminal 54
Live Zero Time-
or par.
Live
4-83