Main Menu - Lonworks - Group 11 - Trane TR200 Programming Manual

Hide thumbs Also See for TR200:
Table of Contents

Advertisement

Parameter Description

Main Menu - LonWorks - Group 11

LonWorks, 11-**
Parameter group for all LonWorks specific parameters.
Parameters related to LonWorks ID.
11-00 Neuron ID
Range:
0 N/A*
[0 - 0 N/A]
11-01 Domain
Range:
0 N/A*
[0 - 0 N/A]
11-02 Subnet ID
Range:
0 N/A*
[0 - 255 N/A]
11-03 Node ID
Range:
0 N/A*
[0 - 255 N/A]
11-10 Drive Profile
Option:
[0] *
VSD profile
[1]
Pump controller
11-15 LON Warning Word
Range:
0 N/A*
[0 - 65535 N/A]
Bit
Status
0
Internal fault
1
Internal fault
2
Internal fault
3
Internal fault
4
Internal fault
5
Invalid type change for nvoAnIn1
6
Invalid type change for nvoAnIn2
7
Invalid type change for nvo109AnIn1
8
Invalid type change for nvo109AnIn2
9
Invalid type change for nvo109AnIn3
10
Initialization error
11
Internal communication error
12
Software revision mismatch
13
Bus not active
14
Option not present
15
LON input (nvi/nci) exceeds limits
4-102
Function:
View the Neuron chip's unique Neuron ID number.
Function:
Function:
Function:
Function:
This parameter allows selecting between LONMARK Functional Profiles.
The Trane Profile and the Node Object are common for all profiles.
Function:
This parameter contains the LON specific warnings.
TR200 Programming Guide

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents