Quick Transfer of Parameter Settings between Multiple Adjustable Frequency Drives
Once the set-up of an adjustable frequency drive is
complete, we recommend that you store the data in
the keypad or on a PC via MCT 10 Set-up Software
Tool.
Data storage in keypad:
1.
Go to par.0-50
LCP Copy
2.
Press the [OK] key.
3.
Select "All to keypad"
4.
Press the [OK] key.
All parameter settings are now stored in the keypad indicated by the progress bar. When 100% is reached, press
[OK].
NOTE
Stop the motor before performing this operation.
You can now connect the keypad to another adjustable frequency drive and copy the parameter settings to this
adjustable frequency drive as well.
Data transfer from the keypad to the adjustable frequency drive:
1.
Go to par.0-50
LCP Copy
2.
Press the [OK] key.
3.
Select "All from keypad"
4.
Press the [OK] key.
The parameter settings stored in the keypad are now transferred to the adjustable frequency drive indicated by
the progress bar. When 100% is reached, press [OK].