Trane TR200 Programming Manual page 126

Hide thumbs Also See for TR200:
Table of Contents

Advertisement

6-5* Analog Output 1
Parameters for configuring the scaling and limits for analog output 1, i.e., Terminal 42. Analog outputs are
current outputs: 0/4–20 mA. Common terminal (terminal 39) is the same terminal and has the same electrical
potential for analog common and digital common connection. Resolution on analog output is 12 bit.
6-50 Terminal 42 Output
Option:
[0] *
No operation
[100]
Output freq. 0-100
[101]
Reference Min-Max
[102]
Feedback +-200%
[103]
Motor cur. 0-Imax
[104]
Torque 0-Tlim
[105]
Torque 0-Tnom
[106]
Power 0-Pnom
[107] *
Speed 0-HighLim
[113]
Ext. Closed-loop 1
[114]
Ext. Closed-loop 2
[115]
Ext. Closed-loop 3
[130]
Out fr 0-100 4-20
[131]
Reference 4-20mA
[132]
Feedback 4-20mA
[133]
Motor cur. 4-20mA
[134]
Torq.0-lim 4-20mA
[135]
Torq.0-nom 4-20mA
[136]
Power 4-20mA
[137]
Speed 4-20mA
[139]
Bus ctrl.
[140]
Bus ctrl. 4-20 mA
[141]
Bus ctrl t.o.
[142]
Bus ctrl 4-20mA t.o.
[143]
Ext. CL 1 4-20 mA
[144]
Ext. CL 2 4-20 mA
[145]
Ext. CL 3 4-20 mA
TR200 Programming Guide
Function:
Select the function of Terminal 42 as an analog current output. A motor
current of 20 mA corresponds to I max .
: 0–100 Hz, (0–20 mA)
: Minimum reference - Maximum reference, (0–20 mA)
: -200% to +200% of par.20-14
: 0 - Inverter Max. Current (par.16-37
: 0 - Torque limit (par.4-16
Torque Limit Motor
: 0 - Motor rated torque, (0–20 mA)
: 0 - Motor rated power, (0–20 mA)
: 0 - Speed High Limit (par.4-13
4-14
Motor Speed High Limit
: 0–100%, (0–20 mA)
: 0–100%, (0–20 mA)
: 0–100%, (0–20 mA)
: 0–100 Hz
: Minimum Reference - Maximum Reference
: -200% to +200% of par.20-14
: 0 - Inverter Max. Current (par.16-37
: 0 - Torque limit (par.4-16
Torque Limit Motor
: 0 - Motor rated torque
: 0 - Motor rated power
: 0 - Speed High Limit (4-13 and 4-14)
: 0–100%, (0–20 mA)
: 0 - 100%
: 0–100%, (0–20 mA)
: 0 - 100%
: 0 - 100%
: 0 - 100%
: 0 - 100%
Parameter Description
Maximum
Reference/Feedb., (0–20 mA)
Inv. Max.
Current), (0–20 mA)
Mode), (0–20 mA)
Motor Speed High Limit [RPM]
[Hz]), (0–20 mA)
Maximum Reference/Feedb.
Inv. Max.
Current)
Mode)
and par.
4-89

Hide quick links:

Advertisement

Table of Contents
loading