Initialization
[3]
Boot mode
14-23 Typecode Setting
Option:
TR200 Programming Guide
5.
Connect to the line power supply.
6.
Carry out various tests.
7.
The results are displayed on the keypad and the adjustable frequen-
cy drive moves into an infinite loop.
8.
par.14-22
Operation Mode
Carry out a power cycle to start up in normal operation after a control
card test.
If the test is OK:
keypad readout: Control Card OK.
Disconnect the line power supply and remove the test plug. The green
LED on the control card will light up.
If the test fails:
keypad readout: Control Card I/O failure.
Replace the adjustable frequency drive or control card. The red LED on
the control card is turned on. To test the plugs, connect/group the fol-
lowing terminals as shown below: (18 - 27 - 32), (19 - 29 - 33) and (42 - 53
- 54).
Initialization
Select
[2] to reset all parameter values to default settings,
except for par.15-03 Power-ups, par.15-04
15-05
Over
Volts. The adjustable frequency drive will reset during the
next power-up.
par.14-22
Operation Mode
operation
[0].
Function:
Typecode re-writing. Use this parameter to set the typecode matching
the specific adjustable frequency drive.
Parameter Description
is automatically set to normal operation.
Over Temps
will also revert to the default setting
and par.
Normal
4-125