Parameter Description
21-0* Extended CL autotuning
The extended PID closed-loop PID controllers (
simplifying and saving time during commissioning, while ensuring accurate PID control adjustment.
To use PID autotuning, it is necessary for the relevant extended PID controller to have been configured for the
application.
A graphical Local Control Panel (keypad) must be used in order to react on messages during the autotuning
sequence.
Enabling autotuning par.21-09
keypad then directs the user with on-screen instructions.
PID autotuning functions by introducing step changes and then monitoring the feedback. From the feedback
response, the required values for PID Proportional Gain, par.21-21
21-41
Ext. 2 Proportional Gain
Time, par.21-22
Ext. 1 Integral Time
3 Integral Time
for EXT CL 3 are calculated. PID Differentiation Time, par.21-23
EXT CL 1, par.21-43
Ext. 2 Differentation Time
3 are set to value 0 (zero). Normal / Inverse, par.21-20
2 Normal/Inverse Control
for EXT CL 2 and par.21-60
during the tuning process.
These calculated values are presented on the keypad and the user can decide whether to accept or reject them.
Once accepted, the values are written to the relevant parameters and PID autotuning mode is disabled in par.
21-09
PID
Autotuning. Depending on the system being controlled the time required to carry out PID autotuning
could be several minutes.
Excessive feedback sensor noise should be removed using the input filter (parameter groups 6-** and 5-5*,
Terminal 53/54 Filter Time Constant/Pulse Filter Time Constant #29/33) before activating PID autotuning.
21-00 Closed-loop Type
Option:
[0] *
Auto
[1]
Fast Pressure
[2]
Slow Pressure
[3]
Fast Temperature
[4]
Slow Temperature
4-170
parameter group 21-**, Ext. Closed-loop
PID Autotuning
puts the relevant PID controller into PID autotuning mode. The
for EXT CL 2 and par.21-61
for EXT CL 1, par.21-42
for EXT CL 2 and par.21-63
Ext. 1 Normal/Inverse Control
Ext. 3 Normal/Inverse Control
Function:
This parameter defines the application response. The default mode
should be sufficient for most applications. If the relative application
speed is known, it can be selected here. This will decrease the time nee-
ded for carrying out PID autotuning. The setting has no impact on the
value of the tuned parameters and is used only for the PID autotuning
sequence.
Ext. 1 Proportional Gain
Ext. 3 Proportional Gain
for EXT CL 3 and Integral
Ext. 2 Integral Time
for EXT CL 2 and par.21-62
Ext. 1 Differentation Time
Ext. 3 Differentation Time
for EXT CL 1, par.21-40
for EXT CL 3 are determined
TR200 Programming Guide
) can each be auto-tuned,
for EXT CL 1, par.
Ext.
for
for EXT CL
Ext.