AFDH Startup Procedure

TR200 Drive Configuration

Note: Technician may elect to configure the drive by
using Danfoss VLT Motion Control tool MCT10.
Follow the following steps:
1. If the TDU Drive Utility Program is installed on your
laptop: You must first uninstall the TDU Drive Utility in
order to install the MCT 10 software.
2. Install MCT 10 toll: HUB Document DOC-155220: MCT
10 Installation Instructions.docx (Danfoss VLT Motion
Control Tools MCT 10 Set-up Software manual)
3. Configure the TR200 drive using MCT 10 tool: HUB
Document DOC-179427: Creating a Project a Master
File and Configuration for AFDH D & E-Frame
Drive.docx (AFDH D & E-Frame Drive Configuration
Instructions Using MCT 10 Tool).
To manually configuring the drive, you should ensure the
drive is at the default sittings by performing the following
procedures to reset the drive:
1. Disconnect power to the drive, and wait for the display
to shut down.
2. While powering up the drive, press and hold the
following keys: Status, Main, and OK.
3. After 5 seconds, release the keys.
After the drive is reset, reprogram the items listed in the
below tables.
Table 27. Job specific settings
Group Parameter Description
1
20
Motor kW
1
24
Motor Current
1
25
Motor Nominal speed Set to nameplate TRPM
4
16
Torque limit mode
4
18
Current limit
Table 28. Trane default settings
Group Parameter Description
0
20
Display line 1.1 small
0
21
Display line 1.2 small
0
22
Display line 1.3 small
0
23
Display line 2 large
0
24
Display line 3 large
Custom Readout Max
0
32
Value
0
40
Hand on key
0
41
Off key
0
60
Main Menu password
Access to main menu w/
0
61
o password
52
Table 28. Trane default settings (continued)
Group Parameter Description
1
1
1
1
3
3
3
3
3
3
4
4
5
5
8
8
8
8
8
8
8
8
14
Value
After all settings are made save a copy chiller service
report for future use. Recommend that Trane Techs load to
Set to nameplate NMKW
ComfortSite by chiller serial number.
Set to nameplate NMRA
Set to maximum
Set to maximum
Setting
DC link voltage
(1630)
Motor Current
(1614)
Heat sink temp
(1634)
Input Power Kw
(1610)
Freq Hz (1613)
Nameplate NMRA
Disabled (0)
Disabled (0)
999
LCP; Read only (1)
03
Torque characteristics
22
Motor voltage
23
Motor frequency
39
Motor poles
02
Minimum Reference
03
Maximum Reference
15
Reference 1 Source
16
Reference 2 Source
41
Ramp 1 ramp up time
42
Ramp 2 ramp down time 20 sec
12
Motor speed low limit
14
Motor speed high limit
12
Terminal 27 Digital Input No operation (0)
40.1
Function Relay
01
Control Site
03
Control Timeout Time
04
Control Timeout Function Stop
30
Protocol
31
Address
32
Baud Rate
33
Parity / Stop Bits
Maximum Response
36
Delay
21
Automatic Restart Time 10 sec
Setting
Variable torque (1)
Nameplate voltage
60 Hz
Poles (2)
30 Hz
60 Hz
No Function
No Function
10 sec
38 Hz
60 Hz
Running
Controlword only (2)
15 sec
Modbus RTU
3
38400 Baud
No Parity, 1 Stop Bit
100
AFDH-SVN004C-EN

Advertisement

Table of Contents
loading

This manual is also suitable for:

CvhfAfdh

Table of Contents