2.3 Outline of Digital Signal Output Circuit

There is a sink type (DX1*0) digital signal output circuit and source type (DX1*1) digital signal
output circuit. Use this circuit within the range shown below.
Output circuit
24VDC(+)
Output conditions
<Caution>
*
When using a conductive load such as a relay, always connect a diode (withstand voltage 100V
or more, 100mA or more) parallel to that load.
*
When using a capacity load such as a lamp, connect a protective resistance (R=150ohm)
serially to that load to limit the rush current. (Make sure that the current is lower than the
tolerable current including the momentary current.)
CAUTION
When using a conductive load such as relays, always contact a diode in parallel to the load as a
noise measure.
When using a capacity load such as a lamp, always connect a protective resistor serially to the
load to suppress rush currents.
2. SYSTEM CONFIGURATION
2.3 Outline of Digital Signal Output Circuit
(Machine side)
RA
PL
(Machine side)
RA
R
Insulation method
Rated load voltage
Max. output current
Output delay time
DO-L/DO-R ((4)/(9))
R
Sink type (DX1*0)
DO-L/DO-R ((4)/(9))
24VDC(+)
PL
Source type (DX1*0)
Non-insulating
+24VDC
60mA/point
40µs
2-9