Input conditions
The input signal must be used within the conditions shown below.
Input voltage when external contact is ON
Input current when external contact is ON
Input voltage when external contact is OFF
Input current when external contact is OFF
Tolerable chattering time
Input signal hold time
Input circuit operation delay time
Machine side contact capacity
Input voltage when external contact is ON
Input current when external contact is ON
Input voltage when external contact is OFF
Input current when external contact is OFF
Tolerable chattering time
Input signal hold time
Input circuit operation delay time
Machine side contact capacity
(Note) The input signal hold time 40ms or more is a reference. The input signal will not be
recognized unless the input signal is held for longer than the ladder process cycle time.
2. SYSTEM CONFIGURATION
2.2 Outline of Digital Signal Input Circuit
Sink type
T2
T1
T3
Source type
T2
T1
T3
2-8
6V or less
9mA or more
20V or more, 25.2V or less
2mA or less
3ms or less
(Refer to T1 in drawing below)
40ms or more
(Refer to T2 in drawing below)
.
=
3ms ≤ T3
.
T4 ≤ 16ms
+30V or more, 16mA or more
T1
T4
18V or more, 25.2V or less
9mA or more
4V or less
2mA or less
3ms or less
(Refer to T1 in drawing below)
40ms or more
(Refer to T2 in drawing below)
.
=
3ms ≤ T3
.
T4 ≤ 16ms
+30V or more, 16mA or more
T1
T4