Make sure that the material level is below all known installations when using the
" Auto false echo suppression wizard" to determine the TVT. Ideally the vessel
should be empty or almost empty.
Note the distance to the material level when determining the echo profile and set
the value in parameter " auto false echo suppression" to a smaller distance to avoid
suppression of the material echo.
If an agitator (whisk) is available, it should be in operation.
As soon as the wizard is successfully completed, parameter " Auto false echo
suppression" is set to " Activated" and the determined TVT curve is used.
Confirm
CONFIRM:
Accepts the settings as the last step in the wizard.
Setting Yes:
The wizard is closed and settings are applied.
Setting No:
The wizard is closed and settings are not applied. They must be entered again when
the wizard is run again.
7.6

Application examples

7.6.1

Application example level

1
2
3
4
5
6
SITRANS LR150
Operating Instructions, 08/2020, A5E50352155
Distance (5.5 m)
Space (4.5 m)
1.0 m
Upper calibration point
Transmitter reference point
9.0 m far range
Setup with the integrated HMI
7.6 Application examples