Quick Commissioning: Level/Space/Distance/Custom - Siemens SITRANS Probe LU240 Compact Operating Instructions

Ultrasonic level transmitters
Table of Contents

Advertisement

Note
Important information regarding the use of commissioning wizard
• A reset to factory defaults should be performed before running "Quick commissioning
wizard" if the device has been used in a previous application.
(Go to menu "Maintenance and diagnostics > Resets", and for parameter "Reset", select
setting "Factory reset".)
• Settings for quick commissioning wizard are inter-related and changes apply only after
"Confirm" is set to 'Yes' in final step.
• Do not use quick commissioning wizard to modify individual parameters. (See instead
chapter "Parameter assignment - Local" in full operating instructions.)
Perform customization for your application only after "Quick commissioning wizard" has
been completed.
Note
Wizard operation requires high mA setting
During wizard operation, the mA reading for device output will equal the setting for
parameter "Upper fault current". When wizard completes, device output will return to normal
behavior.
7.2.7.1

Quick commissioning: Level/Space/Distance/Custom

SITRANS Probe LU240 with mA/HART
Compact Operating Instructions, 09/2021, A5E42673704-AE
Commissioning
7.2 Local commissioning
35