Safety Specification

As assessed to EN ISO13849-1 and EN61800-5-2 the inverter has the following related safety values:-
Criterion
SIL3
SIL3
SIL Capability
PLe
PLe
PLe
Mission Time
Fault Reaction Function
Note: all values quoted in this table are valid only when the two STO user inputs are driven independently. This is as required by EN ISO
13849-1 category 3. See the Alignment to European Standards section in this chapter for the required architecture which must be used
throughout the machine design relevant to the drive under consideration.
1
EN ISO13849 limits MTTFd to 100 years.
2
A detected fault in the STO circuit causes STO to become active, and remain active until after a power cycle.
AC30 series Variable Speed Inverter
Requirement
For type A subsystems, HFT = 1:
SFF ≥ 60%
≥ PFH ≥ 10
-7
-8
10
-
Category 3; PFH ≤ 4,29 x 10
-8
30 years ≤ MTTFd < 100 years
DC = medium
20 years
-
Safe Torque Off
Value achieved
SFF = 99%
-9
PFH = 2.3 x 10
3
-9
PFH = 2.3 x 10
MTTFd = 100 years
1
DC = Medium
20 years
2
Latched STO
8-5