6-10
Associated Equipment - Power Stack

DC Link Input Fuses

DC link input fuse ratings are given in the table below for both European and North American territories.
For North America, the recommended fuses are Mersen A70QS series, 700Vac/dc semiconductor protection fuses (available up to
800A), and Bussmann FWP-A series, 700Vac/dc semiconductor protection fuses (available up to 1200A). These are both UL recognised
components.
Customers can source equivalent fuses for use in their installations.
Note: Where inverters are used on AFE systems with elevated DC link buses above 700V, higher voltage fuses must be used.

AC Motor Chokes (optional)

See page 6-6.
Frame
Product Code
Input Fuse
Size
Rating (A)
7x0-4K0315
K
7x0-4K0380
7x0-4K0440
7x0-4L0530
L
7x0-4L0590
7x0-4M0650
M
7x0-4M0700
N
7x0-4N0790
Europe
North America & Canada
Input Fuse
Fuse Type
Rating (A)
500
500
A70QS series
630
600
A70QS series
800
700
A70QS series
800
800
A70QS series
1000
900
FWP-A series
1000
900
FWP-A series
1000
1000
FWP-A series
1250
1200
FWP-A series
AC30 series Variable Speed Inverter