System Auxiliary 24V Input (Ac30D Only; Digital Inputs (Ac30D Only - Parker AC30P Hardware Installation Manual

Variable speed drive
Hide thumbs Also See for AC30P:
Table of Contents

Advertisement

SYSTEM AUXILIARY 24V INPUT (AC30D ONLY)

+24V AUX input (X30/05), 0V AUX input (X30/06)
Operating Voltage
24V +10%
This is the system auxiliary power input. It is used to power the isolated encoder power supply output (X31/07-08 and
X32/07-08) and the encoder transmit output (X33/01-06).
It will also keep the entire control module (digital I/O, analog I/O, options and GKP) powered when the main stack
power is off.
A common non-earthed SELV supply can be used to power more than one control module, by bussing the supply to
the +24V system aux. input terminal (X30/05) and to the 0V system aux. input terminal (X30/06), on each drive.
Input Current
1.5A minimum supply required, per control module.
2.0A peak current on power-up, per control module.
The supply to these inputs should be suitably externally fused at 2A, at each individual drive, to protect the control
module and supply wiring.
Input Capacitance
150uF nominal.

DIGITAL INPUTS (AC30D ONLY)

DIN1 (X30/01) – DIN3 (X30/03), DIN0V (X30/04)
Conforming to EN61131-2
Nominal Rated Voltage
24V
Operating Range
DIN1, DIN2, DIN3:
0-5V dc = OFF, 15-24V dc = ON
(absolute maximum input voltage ±30V dc)
Input Threshold
Typically 10V
Input Impedance
2.6kΩ
Input Current
9.2mA ± 10% @ 24V
Sample Interval
1ms
Technical Specifications - Control Module
24V
15V
5V
0V
F-5
ON
undefined state
OFF
AC30 series Variable Speed Drive

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac30 seriesAc30vAc30d

Table of Contents