Power Stack Terminal Block Wire Range - Parker AC30P Hardware Installation Manual

Variable speed drive
Hide thumbs Also See for AC30P:
Table of Contents

Advertisement

POWER STACK TERMINAL BLOCK WIRE RANGE

Wire sizes for Europe should be chosen with respect to the inverter operating conditions, in addition to local National Electrical Safety Installation
Requirements. Local wiring regulations always take precedence.
Frame
Size
K
L
M
N
In North America, wire sizes (AWG / kcmil) are based on NEC/NFPA-70 for ampacities of thermoplastic-insulated (75ºC) copper conductors.
The wire sizes allow for an ampacity of 125% of the rated input and output amperes for motor branch-circuit conductors as specified in
NEC/NFPA-70.
Frame
Size
K
AC30 series Variable Speed Inverter
Power Terminals
(minimum/maximum acceptance for aperture)
AC Line (L1, L2 L3) &
DC Link (DC+, DC-)
Output (M1, M2, M3)
M12 post, accepting crimps or lugs up to width 38mm
M12 post. The use of suitably rated bus bar connections is recommended.
M16 post. The use of suitably rated bus bar connections is recommended.
M16 post. The use of suitably rated bus bar connections is recommended.
Product Code
AC Line
(L1, L2, L3)
Normal Duty
7x0-4K0315...
2x 2/0
7x0-4K0380...
2x 4/0
7x0-4K0440...
2x (300)
Heavy Duty
7x0-4K0315...
(350)
7x0-4K0380...
2x 2/0
7x0-4K0440...
2x 4/0
Cables sizes are specified in AWG or (kcmil)
Installation - Power Stack
Earth Connections
Brake (DB)
Power Terminals
DC Link
Output
(DC+, DC-)
(U, V, W)
2x 4/0
2x 3/0
2x (300)
2x (250)
2x (400)
2x (300)
2x 3/0
(400)
2x 4/0
2x 3/0
2x (300)
2x (250)
M8 ring crimp
M10 ring crimp
M10 ring crimp
M10 ring crimp
Brake
(DB)
4/0
(300)
2x 2/0
4/0
(300)
2x 2/0
4-9