6-13
Associated Equipment - Power Stack
Line Synchronisation Card & AC30 Control Module
The control module required for AFE functionality with an AC30 power stack must be either an AC30P or AC30D fitted with the Encoder
Feedback option module 7004-04-00.
The AC30V does not have AFE control capability.
The Line Synchronisation Card LA471892U001 is connected up to the Encoder Feedback option as shown below:
AC30 series Variable Speed Inverter