Example User Wiring

THE WIRING EXAMPLES SHOWN IN THIS SECTION ARE FOR ILLUSTRATION ONLY. THEY ARE NOT TO BE CONSIDERED
FINAL DESIGNS, NOR AS AN ATTEMPT TO CREATE A DESIGN FOR SPECIFIC SOLUTIONS.
THE USER / INSTALLER IS RESPONSIBLE FOR DESIGNING A SUITABLE SYSTEM TO MEET ALL REQUIREMENTS OF THE
APPLICATION INCLUDING ASSESSING AND VALIDATING IT. PARKER WILL NOT ACCEPT ANY LIABILITY FOR FAILURE TO
DO THIS OR FOR ANY CONSEQUENTIAL LOSS OR DAMAGE.

Applications that do not require STO function

DRIVE
START
X13/02
Here the STO inputs X10/01 and X10/03 have been set to the inactive state (tied to +24V). Drive control is performed solely through software with no
inherent safety function. The drive is controlled with its own start and stop pushbuttons.
Note: Only X10/02 or X10/4 must be earthed, i.e. they should not both be earthed otherwise it is possible to create an earth loop.
AC30 series Variable Speed Inverter
24VDC
DRIVE
STOP
X12/01
X10/01 X10/03 X10/06
X10/02
X10/04
X10/05
WARNING
STO inputs X10/01 and X10/03 must be
connected to 24VDC with respect to
terminals X10/02 or X10/04.
STO Status output on X10/05 and X10/06
may be left disconnected.
X12/05
All wiring shown is within the control cubicle.
X12/06
8-19
Safe Torque Off