Application 3: Presets Speeds - Parker AC30P Hardware Installation Manual

Variable speed drive
Hide thumbs Also See for AC30P:
Table of Contents

Advertisement

5-16
Installation - Control Module

APPLICATION 3: PRESETS SPEEDS

Ideal for general purpose applications requiring multiple speed levels
ANIN 01 (X11/01)
SPEED SETPOINT
ANIN 02 (X11/02)
SPEED TRIM
RUN
DIGIN 01 (X13/02)
PRESET SELECT 1
DIGIN 02 (X13/03)
DIGIN 03 (X13/04)
PRESET SELECT 2
PRESET SELECT 3
DIGIN 04 (X12/01)
NOT COAST STOP
DIGIN 05 (X12/02)
DIGIN 06 (X12/03)
NOT QUICKSTOP
DIGIN 07 (X12/02)
TRIP RESET
Presets Speeds Application
This is ideal for applications requiring multiple discrete speed levels.
The setpoint is selected from either the sum of the analogue inputs, (as in Application 1 and known here as PRESET 0), or as one of up to seven
other pre-defined speed levels. These are selected using DIN2, DIN3 and DIN4, refer to the Truth Table above.
P
Edit parameters
1917 to
entering a negative speed setpoint.
Preset Speed 0
1916
Preset Speed 1
1917
Preset Speed 2
1918
Preset Speed 3
1919
Preset Speed 4
1920
Preset Speed 5
1921
Preset Speed 6
1922
Preset Speed 7
1923
0V
0V
0V
0
24V
0V
0V
1
0V
24V
0V
2
24V
24V
0V
3
24V
0V
0V
4
0V
0V
24V
5
24V
24V
0V
6
24V
24V
24V
7
0422
0457
0447
SEQUENCING LOGIC
Seq Stop Method
0484
P
1923 on the keypad to re-define the speed levels of PRESET 1 to PRESET 7. Reverse direction is achieved by
Application 3:
"Speed Presets"
IDEAL FOR GENERAL PURPOSE APPLICATIONS
REQUIRING MULTIPLE DISCRETE SPEED LEVELS
Ref Max Speed Clamp
1265
MIN /MAX SPEED
Ref Min Speed Clamp
1264
F
V
CURRENT LIMIT
V/F SHAPING
I FDBK
Rated Motor Current
Vhz Shape
0455
Base Frequency
Fixed Boost
Acceleration Time
0486
RAMP
Deceleration Time
0487
Stop Ramp Time
0504
Quickstop Ramp Time
0508
F
V
PWM CONTROL
SPEED DEMAND
ANOUT 01 (X11/03)
ANOUT 02 (X11/04)
MOTOR CURRENT
FEEDBACKS
RELAY 01
(X14/01)
if AC30V
(X14/02)
OR
RELAY 11
(X23/01)
Requires IO Option
(X23/02)
7004-01-00
RELAY 02
(X14/03)
if AC30V
(X14/04)
OR
RELAY 12
(X23/03)
Requires IO Option
(X23/04)
7004-01-00
AC30 series Variable Speed Inverter
RUNNING
NOT
TRIPPED

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ac30 seriesAc30vAc30d

Table of Contents