3-2
Product Overview

Power Stack Features

General
Switching Frequency
Output Frequency
Dual Rating
Stack
Trip Conditions
Protection
Current Limit
Overload Rating
User
Line Input
Terminals
Motor Output
PE
DC Input
Brake Output
AC30 series Variable Speed Inverter
Minimum 2kHz (default)
Maximum 8kHz
Derating of output current will apply above the default switching frequency.
Maximum is Switching Frequency divided by 8. This is limited to 590Hz due to export rules.
e.g.
for 2kHz switching frequency it is 2000/8 = 250Hz
Maximum is Switching Frequency divided by 6, in PMAC Motor Closed Loop Control.
If >590Hz is required, please contact your local Parker Sales representative.
Normal duty (ND)
Heavy duty (HD)
Output scct: line-to-line & line-to-earth
Overcurrent:
-
Frame K 220% HD current / Stall
-
Frames L, M & N 190% HD current / Stall
Overvoltage & undervoltage
Heatsink over-temperature
Internal over-temperature
Output current imbalance (Frames L, M & N only)
Missing output current sensor
Missing line phase
Motor Thermistor over-temperature (using GPIO option)
Dynamic Brake scct protection (Frame K only)
Adjustable 110% (ND) or 150% (HD) for 60s
180% shock load limit (Heavy Duty – Frame K only)
Inverse Time
ND - 110% overload for 60s
HD - 180% overload for 3s (Frame K only), 150% overload for 60s
3 AC input terminals L1, L2, L3 (710 stacks only)
3 AC output terminals - M1, M2, M3 (to be used as line supply connections for AFE applications)
2 protective earth terminals
2 DC input terminals DC+ and DC-
1 DC output terminal DB to be used in conjunction with DC+ when connecting a Dynamic Brake
Resistor (Frame K only)