Conducted Emissions Standards - Parker AC30P Hardware Installation Manual

Variable speed drive
Hide thumbs Also See for AC30P:
Table of Contents

Advertisement

A-6
Compliance

CONDUCTED EMISSIONS STANDARDS

The various standards have common roots (CISPR 11 & CISPR14) so there is some commonality in the test levels applied in different standards
and environments.
Product Specific
EN 61800-3
Category C1
Category C2
Category C3
Standards
Generic
EN61000-6-3
EN61000-6-4
Equivalent
Not applicable
Not applicable
Equivalent
These limits have no relationships with
the generic standards.
= Limit decreases with the Log of frequency for the specified frequency range
Limits
Quasi Peak
Frequency (MHz)
(dB/µV)
0.15 - 0.5
66 > 56
0.5 - 5.0
5.0 - 30.0
0.15 - 0.5
0.5 - 5.0
5.0 - 30.0
0.15 - 0.5
100
I ≤100A
0.5 - 5.0
5.0 - 30.0
90 > 70
0.15 - 0.5
130
I ≥100A
0.5 - 5.0
125
5.0 - 30.0
115
Average
(dB/µV)
56 > 46
56
46
60
50
79
66
73
60
73
60
90
86
76
80 > 60
120
115
105
AC30 series Variable Speed Inverter