6-4
Associated Equipment - Power Stack

AC Line Chokes (optional)

AC30 frames K - N have an internal DC link choke. However, in some instances an external AC line choke may also be required.
1. Frame K: when used on supplies delivering more than 18kA but less than 100kA RMS symmetrical Amperes, 480V maximum.
2. Frames L, M & N: when used on supplies delivering more than 65kA but less than 100kA RMS symmetrical Amperes, 480V
maximum.
3. when used to mitigate supply quality issues.
Frame
Size
Notes:
1. Number of supply phases: 3.
2. Supply voltage rating: 480V +10% max IT/TN.
3. Required AC line choke impedance is nominally 3% of the drive rating.
4. Frequency of operation: 50 – 60Hz.
5. Choke inductance during HD overload should be a minimum of 90% nominal inductance.
6. Typical AC line choke harmonic current content:
Motor
Power
Product Code
kW
710-4K0315...
160
K
710-4K0380...
200
710-4K0440...
250
710-4L0530...
280
L
710-4L0590...
315
710-4M0650...
355
M
710-4M0700...
400
N
710-4N0790...
450
Harmonic
Fundamental
th
5
th
7
11
13
Inductance
Rated Current
(mH/phase)
(A)
hp
250
0.095
280
300
0.075
350
350
0.065
430
450
0.055
500
500
0.050
555
550
0.045
605
600
0.040
680
650
0.035
765
Harmonic Current
Content (%)
96
25
8
th
6
th
4
Peak
Instantaneous
Current (A)
@150% HD
rating
485
590
720
930
1040
1150
1260
1435
AC30 series Variable Speed Inverter