Operating functions through HART

7.18 Factory calibration

7.18
Factory calibration
Introduction
You can use factory calibration to reset the transmitter to the factory state.
Description
You can use the menu-guided interface of SIMATIC PDM or HART Communicator to select
the range of parameters to be reset:
1. Current trim
2. Sensor zero point calibration (position correction)
3. Pressure corrections (zero point calibration and sensor trim)
4. All parameters relevant for the processing of measured values, such as zero point, limit
point, electrical damping, display unit, current trim, zero point calibration (position
correction), sensor trim, measuring speed, interrupt current limits, interrupt setting,
overflow ranges of current.
5. Variable mapper. This performs the following setting:
PV= Pressure, SV= Sensor temp., TV= Electronics temp., QV= Non-linearized pressure
PV
SV
TV
QV
See also
Factory calibration - FAQ
(http://support.automation.siemens.com/WW/view/en/10806940/133000)
7.19

Static configuration data

Description
A further menu command in the corresponding operating program allows you to read and
also write a series of sensor-specific material data. With the factory state, this data is pre-
allocated according to the particular device model. These values are not contained in the
"Factory calibration" function; in other words, changes in the device are permanently saved.
List of variable material parameters:
● Flange type
● Flange material
● Remote seal type