Operation
6.5 Local operation
6.5.5.3

Blind setting of full scale value

Introduction
Blind setting resets the full scale value to the upper sensor limit.
Note
Changes in modes 5 and 6 have an exclusive effect on pressure scaling. This does not
affect the scaling for level or customized characteristic curve. Therefore, only measured
pressure values and pressure units are displayed in these modes.
Condition
You are familiar with the correct operation of the transmitter and the associated safety notes.
You have not created any reference pressure and have selected a pressure unit.
Procedure
To the set the full scale value blindly, proceed as follows:
1. Set mode 6.
2. Press the [↑] and [↓] buttons simultaneously for 2 seconds.
6.5.5.4

Blind adjusting of the start of scale value

Introduction
In the case of blind adjustment, adjust the pressure value of the start of scale value
continuously and without a reference pressure.
Note
Changes in modes 5 and 6 have an exclusive effect on pressure scaling. This does not
affect the scaling for level or customized characteristic curve. Therefore, only measured
pressure values and pressure units are displayed in these modes.
You can toggle between rising and falling characteristic curves.
Condition
You are familiar with the correct operation of the transmitter and the associated safety notes.
You have not created any reference pressure and have selected a pressure unit.
90
SITRANS P DS III with HART
Operating Instructions, 06/2013, A5E00047092-09