Loe Timer (2.3.4.); Calibration (2.3.5.) - Siemens SITRANS LR560 Operating Instructions Manual

Radar transmitters (foundation fieldbus)
Hide thumbs Also See for SITRANS LR560:
Table of Contents

Advertisement

8.2.3.4

LOE TIMER (2.3.4.)

Note
When a loss of echo occurs, Loss of Echo (LOE) (Page 196) determines the material level to
be reported when the fail-safe timer expires.
Factory setting:
Setting range:
Purpose:
8.2.3.5

CALIBRATION (2.3.5.)

LOW CALIBRATION POINT (2.3.5.1.)
Factory setting:
Setting range:
Purpose:
Description:
Related parameters:
The point from which level measurement is referenced.
1)
HI CALIBRATION POINT (2.3.5.2.)
Factory setting:
Setting range:
Purpose:
Description:
Related parameters:
The point from which level measurement is referenced.
1)
LR560 (FOUNDATION FIELDBUS)
Operating Instructions, 06/2018, A5E34648692-AE
100 s
0.00 to 7200 seconds
Sets the reaction speed of the device to measurement changes.
40.000 m or 100.000 m
0.000 to 40.000 m or 0.000 to 100.000 m.
Distance from sensor reference point
defined in UNIT (2.3.1.) (Page 122) and displayed on the LCD and in PDM.
Any change to Low Calibration Point will cause the mA setpoints to be
updated.
UNIT (2.3.1.) (Page 122)
FAR RANGE (2.4.2.) (Page 127)
0.000 m
0.000 to 40.000 m or 0.000 to 100.000 m.
Distance from sensor reference point
defined in UNIT (2.3.1.) (Page 122)
When setting the High Calibration Point value, note that echoes are ignored
within NEAR RANGE (2.4.1.) (Page 127).
Any change to High Calibration Point will cause the mA setpoints to be
updated.
NEAR RANGE (2.4.1.) (Page 127)
UNIT (2.3.1.) (Page 122)
Parameter Reference
8.2 SETUP (2.)
to Low Calibration Point. Units are
1)
to High Calibration Point. Units are
1)
123