Operating functions through HART
7.3 Selecting the measuring modes
7.3.7
Measuring mode "Flow rate"
Description
When you activate the "Flow rate" measuring mode, only two other device variables are
active: volumetric flow and mass flow rate. If another block was active earlier, the
corresponding device variables remain inactive and have the "CONSTANT" status. The
"Flow rate" block here represents a series of permanently interconnected functions which
you need to configure with appropriate parameters.
DV
Device variable
MA
Start of scale value
ME
Full scale value
Figure 7-4
Measuring mode "Flow rate"
Functions of the "Flow rate" block
The "Input scaling, pressure" function defines the pressure range of 0 to 2 bar that is
interpreted as 0 and 100% by the following square root extracting function. A process
pressure of 0.5 bar has been assumed in the following figure.
In the "Flow rate" measuring mode, a square root extracting characteristic curve "srlin2" is
plotted with a fixed root application point of 10%.
In the calculation example, the input value for the "root extraction function" is approx. 25 %
for a prevailing process pressure of 0.5 bar. The output value is approximately 50%.