SITRANS
Pressure transmitter
SITRANS P320/P420 (mA/HART)
Operating Instructions
7MF03.0
7MF04.0
06/2018
A5E44852162-AA
Getting Started
Introduction
Safety information
Description
Installing/mounting
Connecting
Operating
Commissioning
Parameter assignment
Functional Safety
Service and maintenance
Diagnostics and
troubleshooting
Technical data
Dimension drawings
Appendix
List of abbreviations
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SITRANS Series

  • Page 1 Getting Started Introduction Safety information SITRANS Description Pressure transmitter SITRANS P320/P420 (mA/HART) Installing/mounting Connecting Operating Instructions Operating Commissioning Parameter assignment Functional Safety Service and maintenance Diagnostics and troubleshooting Technical data Dimension drawings 7MF03.0 7MF04.0 Appendix List of abbreviations 06/2018 A5E44852162-AA...
  • Page 2 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 3: Table Of Contents

    Table of contents Getting Started............................11 Commissioning the device with display..................11 Commissioning the device without display................13 Introduction..............................15 Purpose of this documentation....................15 Document history........................15 Product compatibility......................15 Scope of validity of this document..................15 Checking the consignment.....................16 Transportation and storage....................16 Notes on warranty........................17 Safety information............................19 Precondition for use.......................19 3.1.1 Warning symbols on the device.....................19...
  • Page 4 Table of contents Installing/mounting............................39 Basic safety instructions......................39 5.1.1 Installation location requirements...................41 5.1.1.1 Devices with marine approval....................42 5.1.2 Proper mounting........................42 Installation (except level)......................43 5.2.1 Installation configuration......................43 5.2.2 Installation (except level)......................44 5.2.3 Fastening with the mounting bracket..................45 Installation (level)........................46 5.3.1 Mounting on the container......................47 Installing "Remote seal"......................50 5.4.1 Remote seal installation......................50...
  • Page 5 Table of contents 7.4.2 Enable user PIN........................81 7.4.3 Enabling button lock.......................81 Commissioning............................83 Basic safety instructions......................83 Switching on the supply voltage.....................84 Commissioning the device with display..................85 Commissioning the device without display................87 Application examples......................88 8.5.1 gauge pressure, absolute pressure from the differential pressure series and absolute pressure from the gauge pressure series................88 8.5.1.1 Commissioning for gases.......................88...
  • Page 6 Table of contents 9.2.13 SV selection [15]........................123 9.2.14 Units [16]..........................123 9.2.14.1 Level units [16]........................123 9.2.14.2 Volume units [16].........................124 9.2.14.3 Volume flow units [16]......................124 9.2.14.4 Mass flow units [16]......................125 9.2.15 Temperature units [17]......................126 9.2.16 Lower scaling point [18].......................126 9.2.16.1 Set lower scaling point......................127 9.2.17 Upper scaling point [19].......................128 9.2.17.1...
  • Page 7 Table of contents 9.3.7 Diagnostics functions......................149 9.3.7.1 Limit monitoring and event counter..................149 9.3.7.2 Trend log..........................152 Functional Safety............................153 10.1 Safety concept........................153 10.1.1 Random and systematic errors....................153 10.1.2 SIL-compliant product version....................153 10.1.3 Safety function........................154 10.1.3.1 Device statuses........................156 10.1.3.2 Safety parameters........................156 10.1.4 Operating modes of the device....................157 10.1.5 Device mode........................157 10.1.5.1...
  • Page 8 Table of contents Technical data............................191 13.1 Input.............................191 13.1.1 Gauge pressure........................191 13.1.2 Gauge pressure with front-flush diaphragm.................192 13.1.3 Gauge pressure from the differential pressure series............193 13.1.4 Absolute pressure from the gauge pressure series.............194 13.1.5 Absolute pressure with front-flush diaphragm..............195 13.1.6 Absolute pressure from the differential pressure series............196 13.1.7 Differential pressure and flow....................197 13.1.8...
  • Page 9 Table of contents 14.4.1 Note 3A and EHDG......................239 14.4.2 Connections as per EN and ASME..................239 14.4.3 F&B and pharma flange.......................240 14.4.4 PMC Style..........................244 14.4.5 Special connections......................245 Appendix..............................247 Technical support.........................247 Certificates...........................248 QR code label........................248 Checklist for Functional Safety.....................248 List of abbreviations..........................251 Pressure transmitter abbreviations..................251 Glossary..............................253 Index.................................257...
  • Page 10 Table of contents SITRANS P320/P420 (mA/HART) Operating Instructions, 06/2018, A5E44852162-AA...
  • Page 11: Getting Started

    Getting Started Commissioning the device with display Introduction In this section, you will learn how to commission the device step-by-step. Before you start, please read the following safety information: ● General safety information (Page 19) ● Basic safety information: Installing/mounting ●...
  • Page 12 Getting Started 1.1 Commissioning the device with display 4. Open the cover of the buttons: Figure 1-1 Top view 5. Set the measuring range. Set lower range value/upper range value (without pressure available) (Page 104) Apply lower range value/upper range value (with pressure present) (Page 119) 6.
  • Page 13: Commissioning The Device Without Display

    Getting Started 1.2 Commissioning the device without display Commissioning the device without display Introduction In this section, you will learn how to commission the device step-by-step. Before you start, please read the following safety information: ● General safety information (Page 19) ●...
  • Page 14 Getting Started 1.2 Commissioning the device without display 4. Open the cover of the buttons: Figure 1-2 Top view 5. Operate the buttons as follows: Apply lower range value (with pressure applied) Hold down the button for 3 seconds. Apply upper range value (with pressure applied) Hold down the button for 3 seconds.
  • Page 15: Introduction

    Introduction Purpose of this documentation These instructions contain all information required to commission and use the device. Read the instructions carefully prior to installation and commissioning. In order to use the device correctly, first review its principle of operation. The instructions are aimed at persons mechanically installing the device, connecting it electronically, configuring the parameters and commissioning it, as well as service and maintenance engineers.
  • Page 16: Checking The Consignment

    ● Devices/replacement parts should be returned in their original packaging. ● If the original packaging is no longer available, ensure that all shipments are properly packaged to provide sufficient protection during transport. Siemens cannot assume liability for any costs associated with transportation damages.
  • Page 17: Notes On Warranty

    The content reflects the technical status at the time of publishing. Siemens reserves the right to make technical changes in the course of further development.
  • Page 18 Introduction 2.7 Notes on warranty SITRANS P320/P420 (mA/HART) Operating Instructions, 06/2018, A5E44852162-AA...
  • Page 19: Safety Information

    Safety information Precondition for use This device left the factory in good working condition. In order to maintain this status and to ensure safe operation of the device, observe these instructions and all the specifications relevant to safety. Observe the information and symbols on the device. Do not remove any information or symbols from the device.
  • Page 20: Conformity With European Directives

    If you need additional information not covered by these instructions, contact your local Siemens office or company representative. Note Operation under special ambient conditions...
  • Page 21: Use In Hazardous Areas

    Safety information 3.3 Use in hazardous areas DANGER Using equipment with approval-related restrictions Risk of explosion, damage to property due to operating conditions not in conformity with the approval (e.g. temperature and pressure limits exceeded) ● Take note of the approval restrictions before using the device. You can find the information on this in the current certificates.
  • Page 22 Safety information 3.3 Use in hazardous areas WARNING Loss of safety of device with type of protection "Intrinsic safety Ex i" If the device has already been operated in non-intrinsically safe circuits or the electrical specifications have not been observed, the safety of the device is no longer ensured for use in hazardous areas.
  • Page 23: Description

    Description Area of application Overview Depending on the variant, the pressure transmitter measures corrosive, non-corrosive and hazardous gases, vapors and liquids. You can use the pressure transmitter for the following measuring tasks: ● Gauge pressure ● Absolute pressure ● Differential pressure With the appropriate configuration and the necessary add-on parts (e.g.
  • Page 24 Description 4.1 Area of application Differential pressure and flow rate This version measures corrosive, non-corrosive and hazardous gases, vapors and liquids. You can use this version for the following measurement types: ● Differential pressure, e.g. effective differential pressure ● Gauge pressure, suitable for small positive or negative pressure value ●...
  • Page 25: Structure

    Description 4.2 Structure Structure Depending on a customer-specific order, the device comprises different parts. ① ⑨ Cover over buttons and nameplate with general information Screw for the cover over the buttons ② ⑩ Cover (front), optionally with inspection window Cover (rear) for electrical terminal compart‐ ment ③...
  • Page 26: Nameplate Layout

    Description 4.3 Nameplate layout ① ● The cover over buttons , under which there are 4 buttons, is located on the upper face of the enclosure. The nameplate with general information is located on the cover over buttons. Nameplate layout Nameplate with general information The nameplate with the article number and other important information, such as design details and technical data, is located on the cover over the buttons.
  • Page 27 Description 4.3 Nameplate layout Nameplate with approval information The nameplate with approval information is located on the front of the enclosure. Characteristics of the hazardous area Type of protection Group (gas, dust) Maximum surface temperature (temperature class) Device protection level Figure 4-3 Example Measuring point label...
  • Page 28: Functional Principle

    Description 4.4 Functional principle Nameplate with information on the remote seals The nameplate with information on the remote seals is located on the back of the enclosure. ① ⑦ Diaphragm remote seals of sandwich type Nominal diameter/nominal pressure: 4 inch, 50 mm tube length, CLASS 600 ②...
  • Page 29: How The Electronics Work

    Description 4.4 Functional principle 4.4.2 How the electronics work Description ① ⑧ Measuring cell sensor Buttons ② ⑨ Measuring amplifier Display ③ ⑩ Analog-to-digital converter Connection for external ammeter ④ ⑪ Microcontroller EEPROM ⑤ Digital-to-analog converter Output current ⑥ EEPROM Auxiliary power ⑦...
  • Page 30: Measuring Cell Operation

    Description 4.4 Functional principle ● You can make an uninterrupted current measurement with a low resistance ammeter at ⑩ the connection ● The measuring cell-specific data, electronics data and parameter assignment data are ⑥ saved in two EEPROM modules. The first EEPROM module is linked to the measuring ⑪...
  • Page 31: Measuring Cell For Gauge Pressure

    Description 4.4 Functional principle Overview The following modes of operation are described: ● Gauge pressure ● Absolute pressure ● Differential pressure and flow rate ● Level The following process connections are available, for example: ● G1/2 B, 1/2-14 NPT ● Male thread: M20 ●...
  • Page 32: Measuring Cell For Gauge Pressure, Front-Flush Membrane

    Description 4.4 Functional principle 4.4.3.2 Measuring cell for gauge pressure, front-flush membrane ① ⑤ Reference pressure opening Filling liquid ② ⑥ Measuring cell Gauge pressure sensor ③ Process connection Inlet pressure ④ Seal diaphragm Figure 4-8 Function chart of the measuring cell for gauge pressure, flush mounted diaphragm ⑥...
  • Page 33: Measuring Cell For Absolute Pressure, Front-Flush Membrane

    Description 4.4 Functional principle ⑤ ● The inlet pressure (p ) is transferred to the absolute pressure sensor via the seal ③ ④ diaphragm and the fill fluid , displacing its measuring diaphragm. ● The displacement changes the resistance of the four piezoresistors (bridge circuit) of the absolute pressure sensor.
  • Page 34: Measuring Cell For Absolute Pressure From The Differential Pressure Series

    Description 4.4 Functional principle 4.4.3.5 Measuring cell for absolute pressure from the differential pressure series ① ⑥ Pressure cap Overload diaphragm ② ⑦ Seal diaphragm on the measuring cell Measuring cell filling liquid ③ ⑧ O-ring Reference pressure ④ Measuring cell body Pressure input variable ⑤...
  • Page 35: Measuring Cell For Differential Pressure And Flow Rate

    Description 4.4 Functional principle 4.4.3.6 Measuring cell for differential pressure and flow rate ① ⑥ Inlet pressure P Filling liquid ② ⑦ Pressure cap Seal diaphragm ③ ⑧ O-ring Inlet pressure P ④ ⑨ Measuring cell body Differential pressure sensor ⑤...
  • Page 36: Measuring Cell For Level

    Description 4.4 Functional principle 4.4.3.7 Measuring cell for level ① ⑦ Inlet pressure P Overload diaphragm ② ⑧ Seal diaphragm on the measuring cell Inlet pressure P ③ ⑨ Pressure cap Filling liquid of the measuring cell ④ ⑩ O-ring Capillary tube with the fill fluid of the mounting flange ⑤...
  • Page 37: Remote Seal

    Description 4.6 System configuration Remote seal Product description ● A remote seal measuring system comprises the following elements: – Remote seal – Transmission line, e.g. capillary line – Pressure transmitter. Note Malfunction of the remote seal measuring system If you separate the components of the remote seal measuring system, this results in malfunctioning of the system.
  • Page 38 Description 4.6 System configuration System communication Communication is via the HART protocol, using: ● HART Communicator (load 230 ... 1100 Ω) ● PC with HART modem on which appropriate software is installed, e.g. SIMATIC PDM (load 230 ... 600 Ω) ●...
  • Page 39: Installing/Mounting

    Installing/mounting Basic safety instructions DANGER Pressure applications Danger to personnel, system and environment will result from improper disassembly. ● Never attempt to loosen, remove, or disassemble process connection while vessel contents are under pressure. WARNING Wetted parts unsuitable for the process media Risk of injury or damage to device.
  • Page 40 Installing/mounting 5.1 Basic safety instructions WARNING Incorrect material for the diaphragm in Zone 0 Risk of explosion in the hazardous area. If operated with intrinsically safe supply devices of category "ib" or devices of the flameproof enclosure version "Ex d" and simultaneous use in Zone 0, pressure transmitter explosion protection depends on the tightness of the diaphragm.
  • Page 41: Installation Location Requirements

    ● Prevent severe external stresses and loads from acting on the device. Note Material compatibility Siemens can provide you with support concerning selection of sensor components wetted by process media. However, you are responsible for the selection of components. Siemens accepts no liability for faults or failures resulting from incompatible materials.
  • Page 42: Devices With Marine Approval

    Installing/mounting 5.1 Basic safety instructions NOTICE Direct sunlight Increased measuring errors. ● Protect the device from direct sunlight. Make sure that the maximum ambient temperature is not exceeded. Refer to the information in the section Technical data (Page 191). 5.1.1.1 Devices with marine approval Note For vibrations in the direction of the measuring cell diaphragm, the measuring accuracy of the...
  • Page 43: Installation (Except Level)

    Installing/mounting 5.2 Installation (except level) NOTICE Incorrect mounting The device can be damaged, destroyed, or its functionality impaired through improper mounting. ● Before installing ensure there is no visible damage to the device. ● Make sure that process connectors are clean, and suitable gaskets and glands are used. ●...
  • Page 44: Installation (Except Level)

    Installing/mounting 5.2 Installation (except level) 5.2.2 Installation (except level) Mounting location Verify that the mounting location meets the following conditions: ● Accessible ● Close to the measuring point ● Vibration-free ● Within the permitted ambient temperature values Protect the pressure transmitter from: ●...
  • Page 45: Fastening With The Mounting Bracket

    Installing/mounting 5.2 Installation (except level) 5.2.3 Fastening with the mounting bracket Introduction You mount the pressure transmitter with the mounting bracket as described below: ● On a mounting range ● On a vertical or horizontal pipe (Ø 50 to 60 mm) When securing, observe the torques in the section Torques (Page 229).
  • Page 46: Installation (Level)

    Installing/mounting 5.3 Installation (level) You can then mount the pressure transmitter in different positions: Installation (level) Mounting location Verify that the mounting location meets the following conditions: ● Accessible ● Close to the measuring point ● Vibration-free ● Within the permitted ambient temperature values Protect the pressure transmitter from: ●...
  • Page 47: Mounting On The Container

    Installing/mounting 5.3 Installation (level) Procedure To install the pressure transmitter for level, proceed as follows: 1. Attach the seal to the container's mating flange. Ensure that the seal is centrally positioned and that it does not restrict the movement of the flange's seal diaphragm in any way.
  • Page 48 Installing/mounting 5.3 Installation (level) Assembly on a closed container When taking measurements in a closed container without or with little condensate formation, the negative pressure line is not filled. Lay the line in such a way that condensation pockets do not form. Install a condensation container if required. Formula: Start of scale value: Δp = ρ...
  • Page 49 Installing/mounting 5.3 Installation (level) When taking measurements in a closed container with strong condensate formation, you must fill the negative pressure line (mostly with the condensate of the measured medium) and install a condensate pot. Lock the device using the dual pneumatic block 7MF9017-..A. Formula: Start of scale value: Δp...
  • Page 50: Installing "Remote Seal

    Installing/mounting 5.4 Installing "Remote seal" Installing "Remote seal" 5.4.1 Remote seal installation General installation instructions ● Keep the measuring system in the factory packing until it is installed in order to protect it from mechanical damage. ● When removing from the factory packing and installing: ensure that damage to and mechanical deformations in the membrane are prevented.
  • Page 51: Installation Of The Remote Seal With The Capillary Line

    Installing/mounting 5.4 Installing "Remote seal" Using remote seals with pressure measuring device for hazardous areas: ● When using remote seals with pressure transmitters in hazardous areas, the permissible ambient temperature limits for the pressure transmitter must not be exceeded. Hot surfaces on the cooling section (capillaries or cooling elements) are a possible source of ignition.
  • Page 52 Installing/mounting 5.4 Installing "Remote seal" Installation type for differential pressure and flow rate measurements Installation type D Start of scale value: - ρ * g * H start Full scale value: - ρ * g * H Legend Start of scale value to be adjusted Full scale value to be adjusted Start of scale value start...
  • Page 53 Installing/mounting 5.4 Installing "Remote seal" Full scale value to be adjusted ρ Density of the measured medium in the container ρ Density of the filling oil in the capillary line of the remote seal Local gravitational acceleration Start of scale value Full scale value Gland distance Installation type G...
  • Page 54: Removing

    Installing/mounting 5.5 Removing ≤ 7 m (23 ft), for halocarbon oil, however only H1 ≤ 4 m(13.1 ft) Start of scale value: = ρ * g * H - ρ * g * H Full scale value: = ρ * g * H - ρ...
  • Page 55: Rotating The Display

    Installing/mounting 5.6 Rotating the display Rotating the display To read the display in any mounting position, you have the option of gradually rotating the display 360°. Procedure 1. Switch off the power supply. 2. Use a 3 mm Allen key to loosen the front safety catch. 3.
  • Page 56 Installing/mounting 5.6 Rotating the display 5. Rotate the display to the desired position. Ensure that the flat ribbon cable of the display remains behind the holder when rotating the display. 6. Press the display into the holder until it engages. SITRANS P320/P420 (mA/HART) Operating Instructions, 06/2018, A5E44852162-AA...
  • Page 57: Rotating The Enclosure

    Installing/mounting 5.7 Rotating the enclosure Rotating the enclosure Introduction To make the device easier to operate in any mounting position, you have the option of adjusting the position of the enclosure within a range of 360°. ① Retaining screw ① One retaining screw for the aluminum enclosure and two retaining screws (front and back) for the stainless steel enclosure prevent that the flat ribbon cable is damaged while rotating...
  • Page 58 Installing/mounting 5.7 Rotating the enclosure Rotating the aluminum enclosure ① 1. Loosen the retaining screw by half a rotation. 2. Rotate the enclosure to the desired position (but no further than the end stop). 3. Tighten the retaining screw. Rotating the stainless steel enclosure 1.
  • Page 59: Connecting

    Connecting Basic safety instructions WARNING Unsuitable cables, cable glands and/or plugs Risk of explosion in hazardous areas. ● Use only cable glands/plugs that comply with the requirements for the relevant type of protection. ● Tighten the cable glands in accordance with the torques specified in Technical data (Page 191).
  • Page 60 Connecting 6.1 Basic safety instructions WARNING Improper laying of shielded cables Risk of explosion through compensating currents between hazardous area and the non‑hazardous area. ● Shielded cables that cross into hazardous areas should be grounded only at one end. ● If grounding is required at both ends, use an equipotential bonding conductor. WARNING Connecting device in energized state Risk of explosion in hazardous areas.
  • Page 61 Connecting 6.1 Basic safety instructions NOTICE Condensation in the device Damage to device through formation of condensation if the temperature difference between transportation or storage and the mounting location exceeds 20 °C (36 °F). ● Before taking the device into operation let the device adapt for several hours in the new environment.
  • Page 62: Connecting The Device

    Connecting 6.2 Connecting the device Connecting the device 6.2.1 Opening the device Procedure ① Safety catch (optional) ② Cover of the electrical cable compartment. Figure 6-1 Rear view of pressure transmitter ① 1. Use a 3 mm Allen key to loosen the safety catch ②...
  • Page 63: Connecting The Device

    Connecting 6.2 Connecting the device 6.2.2 Connecting the device Procedure - Test + ① ⑥ Feed separator with integrated load Safety catch ② ⑦ Supply voltage Process connec‐ tion ③ ⑧ Cable gland for supply voltage/current output Protective conduc‐ tor connector/equi‐ potential bonding terminal ④...
  • Page 64: Closing The Device

    Connecting 6.2 Connecting the device ④ 3. Connect the wires to the connecting terminals "+" and "-". Ensure the correct polarity! ⑨ 4. Apply the shield to the screw of the ground terminal The screw of the ground terminal is electrically connected to the external protective conductor connection.
  • Page 65: Connect The Han Cable Socket To The Cable

    Connecting 6.3 Connect the Han cable socket to the cable 4. Tighten the screw for the cover over the buttons. ⑤ ② 5. Check the tightness of the blanking plug and cable gland in accordance with the degree of protection. Connect the Han cable socket to the cable WARNING Loss of the safety required for approval by using the Han plug...
  • Page 66: Connect M12 Cable Socket To The Cable

    Connecting 6.4 Connect M12 cable socket to the cable Connect M12 cable socket to the cable Procedure WARNING Loss of safety required for approval by using the Han plug The connector may only be used for Ex ia devices and non-Ex devices; otherwise the safety required for the approval is not guaranteed.
  • Page 67 Connecting 6.4 Connect M12 cable socket to the cable Pin assignment Assignment diagram M12-cable socket Layout for M12 device connector ① ① M12 x 1 thread Positioning slot ② Positioning catch Not connected Not connected Shield Shield Middle contact of the cable socket not connected SITRANS P320/P420 (mA/HART) Operating Instructions, 06/2018, A5E44852162-AA...
  • Page 68 Connecting 6.4 Connect M12 cable socket to the cable SITRANS P320/P420 (mA/HART) Operating Instructions, 06/2018, A5E44852162-AA...
  • Page 69: Operating

    Operating Introduction Introduction You operate the device using the keys. If you have a device with a display, you can view the measured values, parameter values and messages. If you have a device without a display, you also have several functions available: Commissioning the device without display (Page 87) Buttons The four buttons are located below the cover:...
  • Page 70: Operating The Device With Display

    Operating 7.2 Operating the device with display Operating the device with display 7.2.1 Display This display has three different views. ● Measurement view ● Parameter view ● Edit view ① Display of: ● Name and unit of measured values (Measurement view) ●...
  • Page 71: Navigating In The Views

    Operating 7.2 Operating the device with display 7.2.2 Navigating in the views Requirement You have opened the cover of the buttons: Figure 7-2 Top view SITRANS P320/P420 (mA/HART) Operating Instructions, 06/2018, A5E44852162-AA...
  • Page 72: Measurement View

    Operating 7.2 Operating the device with display Procedure You navigate in the views with the buttons: Views Buttons Measurement view After the initialization, the measurement view is displayed. 1. Select a random measured value with the buttons 2. Change to the parameter view with the button.
  • Page 73: Display Of Measured Values

    Operating 7.2 Operating the device with display The bar display shows the following information: ● The position of a measured value within the set measuring span (e.g. pressure). ● The position of the temperature value within the sensor limits. ● The scaling of the process values calculated from the pressure value (e.g. volume flow). 7.2.3.1 Display of measured values The following measured values are always displayed:...
  • Page 74: Navigating In The Measurement View

    Operating 7.2 Operating the device with display 7.2.3.2 Navigating in the measurement view Requirement You have disabled the button lock. Disabling button lock (Page 131) Procedure 1. Use the buttons to navigate in the measurement view. 2. To switch to the parameter view, press the button.
  • Page 75 Operating 7.2 Operating the device with display Parame‐ Parameter name on Meaning ter ID the display SQRT POINT Application point for volume flow and mass flow (VSLN and MSLIN) (Page 115) ZERO POINT Zero point adjustment (Page 116) APPLY LRV Apply lower range value (with pressure applied) (Page 118) APPLY URV Apply upper range value (with pressure applied) (Page 118)
  • Page 76: Navigating In The Parameter View

    Operating 7.2 Operating the device with display 7.2.4.2 Navigating in the parameter view Requirement The button lock is disabled. Disabling button lock (Page 131) Procedure 1. Use the buttons to navigate within the parameters. To navigate faster, keep the button pressed. After the last parameter, you jump to the first parameter, and vice versa.
  • Page 77: Changing Parameter Values

    You can learn about retro-installations and obtain additional information on SIMATIC PDM on the Internet at SIMATIC PDM (www.siemens.com/simatic- pdm). SIMATIC PDM monitors the process values, alarms and status signals of the device. The software enables the display, comparison, adjustment, testing and simulation of device data and the setting of calibration and maintenance due dates.
  • Page 78: Locking The Device

    SIMATIC PDM software. Once you have installed SIMATIC PDM on your computer, you can find the manual under: Start > Programs > Siemens Automation > SIMATIC > Documentation. Link to our website: SIMATIC PDM instructions and manuals (https:// support.industry.siemens.com/cs/products?dtp=Manual&pnid=16983&lc=en-WW).
  • Page 79: Setting The Jumper

    Operating 7.4 Locking the device Write protection Sym‐ Read measured values on Read parameters on the Change parameters the display display via the device with dis‐ play Jumper set User PIN enabled Yes, after input of the user PIN Button lock enabled The user PIN is factory set to 2457 in the device.
  • Page 80 Operating 7.4 Locking the device 3. Remove the display from the holder. ① Figure 7-6 Position of the jumper on the board of the device as delivered ① 4. Set the jumper as follows: Result When the jumper is set, only the measured values can be read. The display changes automatically between the measured values.
  • Page 81: Enable User Pin

    Operating 7.4 Locking the device 7.4.2 Enable user PIN Requirement The User PIN is disabled. Procedure 1. Navigate into the parameter view. AUTOHOTSPOT 2. Select the parameter "User PIN" [27]. 3. Use the button to confirm. The message "USER PIN ON" (User PIN enabled) appears for 2 seconds. Result The user PIN is enabled.
  • Page 82 Operating 7.4 Locking the device Result ● The display automatically returns to the measurement view. ● The display automatically changes between the measured values every 12 seconds. ● The symbol for button lock "LL" and the measured value ID are displayed alternately. Note For a device without display, you activate the button lock using remote operation.
  • Page 83: Commissioning

    Commissioning Basic safety instructions DANGER Toxic gases and liquids Danger of poisoning when venting the device: if toxic process media are measured, toxic gases and liquids can be released. ● Before venting ensure that there are no toxic gases or liquids in the device, or take the appropriate safety measures.
  • Page 84: Switching On The Supply Voltage

    Commissioning 8.2 Switching on the supply voltage WARNING Opening device in energized state Risk of explosion in hazardous areas ● Only open the device in a de-energized state. ● Check prior to commissioning that the cover, cover locks, and cable inlets are assembled in accordance with the directives.
  • Page 85: Commissioning The Device With Display

    Commissioning 8.3 Commissioning the device with display Procedure Switch on the power supply. ● Product name and firmware version appear briefly on the display. ● The measured values are shown on the display. For a device without a display, you read off the current output as follows: –...
  • Page 86 Commissioning 8.3 Commissioning the device with display 4. Open the cover of the buttons: Figure 8-1 Top view 5. Set the measuring range. Set lower range value/upper range value (without pressure available) (Page 104) Apply lower range value/upper range value (with pressure present) (Page 119) 6.
  • Page 87: Commissioning The Device Without Display

    Commissioning 8.4 Commissioning the device without display Commissioning the device without display Introduction In this section, you will learn how to commission the device step-by-step. Before you start, please read the following safety information: ● General safety information (Page 19) ●...
  • Page 88: Application Examples

    Commissioning 8.5 Application examples 4. Open the cover of the buttons: Figure 8-2 Top view 5. Operate the buttons as follows: Apply lower range value (with pressure applied) Hold down the button for 3 seconds. Apply upper range value (with pressure applied) Hold down the button for 3 seconds.
  • Page 89 Commissioning 8.5 Application examples Procedure Example: Measuring gases above the Example: Measuring gases below the pressure tapping point pressure tapping point ① ⑤ Pressure transmitter Pressure line ② ⑥ Shut-off valve Shut-off valve ③ ⑦ Shut-off valve to process Shut-off valve (optional) ④...
  • Page 90: Commissioning With Steam Or Liquid

    Commissioning 8.5 Application examples ⑥ 5. Open the shut-off valve at the pressure tapping point. ③ 6. Open the shut-off valve for the process 8.5.1.2 Commissioning with steam or liquid Requirement All valves are closed. Procedure ① Pressure transmitter ② Shut-off valve ③...
  • Page 91: Differential Pressure And Volume Flow

    Commissioning 8.5 Application examples ⑥ 5. Open the shut-off valve at the pressure tapping point. ③ 6. Open the shut-off valve for the process 8.5.2 Differential pressure and volume flow 8.5.2.1 Commissioning in gaseous environments Requirement All shut-off valves are closed. Procedure Pressure transmitter above the differential pressure transducer...
  • Page 92: Commissioning With Liquids

    Commissioning 8.5 Application examples ③ ④ 3. Open the differential pressure valve ( 4. Check and, if necessary, correct the zero point when the start-of-scale value is 0 bar (4 mA). ② 5. Close the stabilizing valve ③ ④ 6. Open the other differential pressure valve ( 8.5.2.2 Commissioning with liquids Requirement...
  • Page 93 Commissioning 8.5 Application examples ② ⑧ Stabilizing valve Gas collector vessels (optional) ③ ④ ⑨ Differential pressure valves Differential pressure transducer ⑤ ⑩ Differential pressure lines Vent valves ⑥ ⑪ Shut-off valves 5-way valve manifold To commission the pressure transmitter for liquids, proceed as follows: ⑥...
  • Page 94: Commissioning With Vapor

    Commissioning 8.5 Application examples 8.5.2.3 Commissioning with vapor Requirement All valves are closed. WARNING Hot vapor Danger of injury or damage to device. ⑥ ③ If the shut-off valves and the differential pressure valve are both open and the stabilizing ②...
  • Page 95 Commissioning 8.5 Application examples Procedure ① ⑦ Pressure transmitter Drain valves ② ⑧ Stabilizing valve Condensate pots ③ ⑨ Differential pressure valves Differential pressure transducer/Orifice plate ④ ⑤ ⑩ Differential pressure lines Insulation ⑥ ⑪ Shut-off valves 3-way valve manifold To commission the pressure transmitter for vapor, proceed as follows: ⑥...
  • Page 96 Commissioning 8.5 Application examples 12.For the start of scale value 0 bar, check the zero point (4 mA). ⑤ If the differential pressure lines have equally high condensate columns with the same temperature, the measurement result is error-free. Otherwise, repeat the zero-point adjustment.
  • Page 97: Parameter Assignment

    Parameter assignment Overview of parameters and functions Introduction You can operate the device via local operation or remote operation (e.g. HART communicator, SIMATIC PDM). ● The parameters that you can reach over the device with a display are marked by the parameter ID.
  • Page 98 Parameter assignment 9.1 Overview of parameters and functions Current output SIMATIC PDM Device with display (lo‐ Device without display cal operation) (local operation) Set fault current "Settings > Current out‐ Select fault current Commissioning the de‐ put" parameter group [10] (Page 120) vice without display (Page 13) Lower fault current...
  • Page 99 Parameter assignment 9.1 Overview of parameters and functions Simulation SIMATIC PDM Device with display (lo‐ Device without display cal operation) (local operation) Simulate fixed pressure value / simulate ramp Menu command "De‐ vice > Simulation > Process values" Identification SIMATIC PDM Device with display (lo‐...
  • Page 100 Parameter assignment 9.1 Overview of parameters and functions HART communication SIMATIC PDM Device with display (lo‐ Device without display cal operation) (local operation) Enable or disable the device identification via Menu command "De‐ Identify the device [34] HART vice > "Squawk" (Page 139) Select secondary variable (SV) "Settings >...
  • Page 101: Parameter Assignment Over Device With Display

    Parameter assignment 9.2 Parameter assignment over device with display Reset SIMATIC PDM Device with display (lo‐ Device without display cal operation) (local operation) Restore ordered configuration Menu command "De‐ Restore ordered con‐ vice > Reset > Restore figuration (Page 141) ordered configuration"...
  • Page 102: Display Of The Pressure Units

    Parameter assignment 9.2 Parameter assignment over device with display Both parameters are available using a local operation or over the remote operation. Example ① ② Pressure units and Pressure reference (alternating) See also Pressure reference [33] (Page 139) 9.2.1.1 Display of the pressure units Certain units are displayed differently on the display and over remote operation.
  • Page 103: Setting The Pressure Units

    Parameter assignment 9.2 Parameter assignment over device with display Setting range: Display (header line) Display (enumeration) Remote operation mbar mbar mbar G/cm2 G/cm2 g/cm KG/cm2 KG/c2 kg/cm KGF/cm2 KF/c2 kgf/cm² mmH2O mmW68 mH2O(4 °C) O (4 °C) inH20 inW68 inH2O(4 °C) inW4 O (4 °C) mmHG...
  • Page 104: Set Lower Range Value [02]/Set Upper Range Value [03]

    Parameter assignment 9.2 Parameter assignment over device with display Result ● The selected pressure unit and pressure reference are displayed as alternating values in the measurement view. ● If the converted pressure measurement has more than 5 digits, "#####" appears in the measurement view.
  • Page 105: Damping Value [04]

    Parameter assignment 9.2 Parameter assignment over device with display Requirement ● No pressure is present. ● You have a device with display. Procedure 1. Navigate into the parameter view. Navigating in the views (Page 71) 2. In the parameter view, set the "Lower range value" parameter [02]. 3.
  • Page 106: Set Damping Value

    Parameter assignment 9.2 Parameter assignment over device with display 9.2.3.1 Set damping value Procedure 1. Navigate to the parameter view. Navigating in the views (Page 71) 2. Select the "Damping value" parameter. 3. Press the button. 4. Set the damping with the buttons.
  • Page 107 Parameter assignment 9.2 Parameter assignment over device with display Figure 9-1 Flow diagram You have various options for setting the measuring task of your device: Device with display Remote operation "Application" parameter [05] Settings > Select output > Application or using the Quick start wizard SITRANS P320/P420 (mA/HART) Operating Instructions, 06/2018, A5E44852162-AA...
  • Page 108: Pressure Measurement

    Parameter assignment 9.2 Parameter assignment over device with display Setting range: Application Characteristic curve Pressure PRESS Linear, proportional to pressure Level LEVEL Linear, proportional to level Volume flow VSLN Linear, square root Proportional to flow rate, linear up to the application pointApplication point [06] (Page 115) VSOFF Hold at 0, square root...
  • Page 109: Level Measurement

    Parameter assignment 9.2 Parameter assignment over device with display ● If the device is set for pressure measurement, no other measured variables (e.g. volume flow) are available. Example For the pressure measurement, you set the following values, for example: Damping value: 2.0 s Lower range value: 0.0 bar...
  • Page 110 Parameter assignment 9.2 Parameter assignment over device with display Example For the level measurement, you set the following values, for example: Damping value: 2.0 s Lower range value: 0.0 bar Upper range value: 5.0 bar Application: Level (LEVEL) Unit: Lower scaling point: 0.0 m Upper scaling point: 49 m...
  • Page 111: Volume And Mass Flow Measurements

    Parameter assignment 9.2 Parameter assignment over device with display 9.2.4.3 Volume and mass flow measurements The following characteristic curves are available for volume and mass flow measurements: ● Hold at 0, square root (VSOFF, for volume or MSOFF, for mass flow) The loop current is 4 mA up to the application point (low flow cut-off (Page 128)).
  • Page 112 Parameter assignment 9.2 Parameter assignment over device with display ● Two step linear, square root (VSLN2, for volume or MSLN2, for mass flow) The loop current has a proportional relationship with the flow rate, two step linear up to the application point (Page 115).
  • Page 113 Parameter assignment 9.2 Parameter assignment over device with display Loop current or flow Set measuring span Example: Volume flow (linear) For the volume flow measurement, you set the following values, for example: Damping value: 2.0 s Lower range value: 0.0 mbar Upper range value: 0.6 bar Application:...
  • Page 114: Volume Measurement

    Parameter assignment 9.2 Parameter assignment over device with display 9.2.4.4 Volume measurement For the volume measurement, the device uses tank characteristic curves for various vessel shapes. Display Vessel Description CYLIN Cylinder vessel SPHER Sphere vessel LINR Linear vessel CONIC Conical bottom vessel ①...
  • Page 115: Set Application

    Parameter assignment 9.2 Parameter assignment over device with display Example For the volume measurement, you set the following values, for example: Damping value: 2.0 s Lower range value: 0.0 mbar Upper range value: 500.0 mbar Application: Cylinder vessel (CYLIN) Unit: Lower scaling point: 0.0 m Upper scaling point:...
  • Page 116: Zero Point Adjustment [07]

    Parameter assignment 9.2 Parameter assignment over device with display 9.2.6 Zero point adjustment [07] Introduction A series of factors, such as installation, static pressure, temperature or long-term stability, can cause zero-point errors. The following options are available to correct zero-point errors: Device without display Device with display Remote operation...
  • Page 117: Adjusting The Zero Point (Differential Pressure)

    Parameter assignment 9.2 Parameter assignment over device with display Result ● The device displays the pressure measurement 0 in the set unit. ● The effective measuring range is reduced by the amount of the upstream pressure. Example: With an upstream pressure of 100 mbar, the effective measuring range of a 1- bar pressure transmitter is reduced to a point between 0 and 0.9 bar.
  • Page 118: Apply Lower Range Value [08]/Apply Upper Range Value [09]

    Parameter assignment 9.2 Parameter assignment over device with display Procedure 1. In the parameter view, select the "Zero point adjustment" parameter [07]. 2. Navigate into the parameter view. Navigating in the views (Page 71) 3. Press the button. 4. The value "0" appears on the display. 5.
  • Page 119: Apply Lower Range Value/Upper Range Value (With Pressure Present)

    Parameter assignment 9.2 Parameter assignment over device with display 9.2.7.3 Apply lower range value/upper range value (with pressure present) Introduction The lower range value (4 mA) corresponds to 0% of the measuring range. The upper range value (20 mA) corresponds to 100% of the measuring range. With pressure present, you have the following options for assigning the desired pressure measurements to the lower range value and the upper range value: Device without display...
  • Page 120: Select Fault Current [10]

    Parameter assignment 9.2 Parameter assignment over device with display Procedure 1. Navigate into the parameter view. Navigating in the views (Page 71) 2. Select the "Apply lower range value" parameter [08]. 3. Press the button. The existing pressure is displayed. 4.
  • Page 121: Upper Fault Current [12]

    Parameter assignment 9.2 Parameter assignment over device with display 20.5 mA 20 mA 22.8 mA 3.55 mA 3.8 mA 4 mA ① Normal operation ② Lower fault current (factory setting) ③ Lower saturation limit (factory setting) ④ Upper saturation limit (factory setting) ⑤...
  • Page 122: Upper Saturation Limit [14]

    Parameter assignment 9.2 Parameter assignment over device with display 20.5 mA 20 mA 22.8 mA 3.55 mA 3.8 mA 4 mA ① Normal operation ② Lower fault current (factory setting) ③ Lower saturation limit (factory setting) ④ Upper saturation limit (factory setting) ⑤...
  • Page 123: Sv Selection [15]

    Parameter assignment 9.2 Parameter assignment over device with display 9.2.13 SV selection [15] Sets a measured value as a secondary variable (SV). Setting range: TEMP Sensor temperature ETEMP Electronics temperature LEVEL Level Volume VFLOW Volume flow USER Custom MFLOW Mass flow Factory setting: As specified in order 9.2.14...
  • Page 124: Volume Units [16]

    Parameter assignment 9.2 Parameter assignment over device with display This parameter is only visible when you have selected the "Level" characteristic curve using the "Application" parameter. Setting range: Factory setting: 9.2.14.2 Volume units [16] Selects the unit for the "Volume" measurement. This parameter is only visible when you have selected a volume characteristic curve using the "Application"...
  • Page 125: Mass Flow Units [16]

    Parameter assignment 9.2 Parameter assignment over device with display Certain units are displayed differently on the display and over remote operation. (Page 102) Setting range: Display (header line) Display (enumeration) Remote operation m3/sec m3/S m³/s m3/min m3/m m³/min m3/h m3/h m³/h m3/d m3/d...
  • Page 126: Temperature Units [17]

    Parameter assignment 9.2 Parameter assignment over device with display Certain units are displayed differently on the display and over remote operation. (Page 102) Setting range: Display (header line) Display (enumeration) Remote operation KG/Sec KG/S kg/s Gr/Sec Gr/min g/min Gr/h KG/min KG/m kg/min KG/h...
  • Page 127: Set Lower Scaling Point

    Parameter assignment 9.2 Parameter assignment over device with display Level Setting range: Freely selectable numeric value Factory setting: Volume Setting range: Freely selectable numeric value Factory setting: Volume flow Setting range: Freely selectable numeric value Factory setting: Setting range: Freely selectable numeric value Factory setting: Mass flow Setting range:...
  • Page 128: Upper Scaling Point [19]

    Parameter assignment 9.2 Parameter assignment over device with display 9.2.17 Upper scaling point [19] Sets the upper range value for the scaling. Depending on the application of the device, you set the upper scaling point as follows: Level Setting range: Freely selectable numeric value Factory setting: 100 m...
  • Page 129: Vessel Dimension A [21]

    Parameter assignment 9.2 Parameter assignment over device with display The parameter is visible when you have selected the "Hold at 0, square root" (VSOFF or MSOFF) characteristic curve using the "Application" parameter. Setting range: 0% - 100% Factory setting: See also Volume and mass flow measurements (Page 111) 9.2.19 Vessel dimension A [21]...
  • Page 130: Button Lock [23]

    Parameter assignment 9.2 Parameter assignment over device with display 9.2.21 Button lock [23] Enables the button lock. You can continue operating the device via HART. Setting range: Button lock enabled Button lock disabled Factory setting: 9.2.21.1 Enabling button lock Procedure 1.
  • Page 131: Disabling Button Lock

    Parameter assignment 9.2 Parameter assignment over device with display 9.2.21.2 Disabling button lock Procedure To disable the button lock, press and hold the button for 5 seconds. Result ● The symbol for Button lock "LL" is hidden. ● You can operate the device using the buttons. Note For a device without display, you deactivate the button lock using remote operation.
  • Page 132: Recovery Id [25]

    Parameter assignment 9.2 Parameter assignment over device with display 5. Enter the new user PIN with a value between 1 and 65535. Changing parameter values (Page 77) 6. Use the button to confirm. 7. Repeat the new user PIN and use the button to confirm.
  • Page 133: Pin Recovery [26]

    You can find the serial number of the device on the nameplate or via remote operation. Siemens Technical Support will give you a PUK (PIN Unlock Key) that you use to reset the user PIN to the factory setting 2457.
  • Page 134: User Pin [27]

    Parameter assignment 9.2 Parameter assignment over device with display 3. Enter the digits of the PUK: – Use the button to change. – Use the button to confirm. – Use the button to delete. The complete PUK is shown on the top line of the display. 4.
  • Page 135: Disable User Pin

    Parameter assignment 9.2 Parameter assignment over device with display Procedure 1. Navigate into the parameter view. Navigating in the views (Page 71) 2. Select the parameter "User PIN" [27]. 3. Use the button to confirm. The message "USER PIN ON" (User PIN enabled) appears for 2 seconds. Result The user PIN is enabled.
  • Page 136: Active Device Mode [28]

    Parameter assignment 9.2 Parameter assignment over device with display Result The User PIN is disabled. 9.2.26 Active device mode [28] Shows the mode in which the device is operated. The parameter is only visible for devices with Functional Safety. Setting range: Functional Safety is disabled FUNCT Validation of the safety-related parameters and/or the fail-...
  • Page 137: Loop Test [31]

    Parameter assignment 9.2 Parameter assignment over device with display 9.2.29 Loop test [31] Sets a constant loop current for test purposes. You have the option of selecting preset values or a user-defined value. Setting range: 3.55 mA 4 mA 12 mA 20 mA 22.8 mA USER...
  • Page 138: Loop Test With User Defined Loop Current Value

    Parameter assignment 9.2 Parameter assignment over device with display 9.2.29.2 Loop test with user defined loop current value Procedure 1. Navigate into the parameter view. Navigating in the views (Page 71) 2. In the parameter view, select the "Loop test" parameter [31]. 3.
  • Page 139: Pressure Reference [33]

    Parameter assignment 9.2 Parameter assignment over device with display LOOPC Loop current (PA) CVOLT Terminal voltage (PB) Factory setting: PRESS Note To have the process value for "Level", "Volume", "Mass flow", "Volume flow" or "Customized characteristic curve" shown as the "Start view", first set the associated characteristic curve using the "Application"...
  • Page 140: Reset [35]

    Parameter assignment 9.2 Parameter assignment over device with display 9.2.33 Reset [35] Used to reset the following settings: Setting range: Restore ordered configuration CUST Reset to sensor calibration SENSR Reset DAC trim to the factory setting Factory reset FACT 9.2.33.1 Reset to sensor calibration Resets the zero point adjustment and sensor calibration to the factory setting.
  • Page 141: Restore Ordered Configuration

    Parameter assignment 9.2 Parameter assignment over device with display 9.2.33.3 Restore ordered configuration With this function you return your device to its delivery state. ● The ordered configuration of the following parameters is restored: – Pressure units – Quick start –...
  • Page 142: Parameter Assignment Over Remote Operation

    Parameter assignment 9.3 Parameter assignment over remote operation Parameter assignment over remote operation 9.3.1 Introduction Introduction This section describes the most important parameters and functions that are available additionally over remote operation: ● "Quick Start" wizard ● Identification (TAG) ● Simulation ●...
  • Page 143: Identification

    Factory setting Short tag Long tag (TAG) Description Message Installation date dd.mm.yyyy Device Manufacturer_id Siemens Product name SITRANS P420 Article number e.g. 7MF0440-1GL01-5AF2-Z Order option 1/ Order option 2 e.g. A01+C11+C12+C14+C20+E00+H01+Y01+Y15+Y21 Serial number in accordance with the measuring cell selection/device manufac‐...
  • Page 144: Simulate Constant Pressure Values

    Parameter assignment 9.3 Parameter assignment over remote operation NOTICE Timeout of simulation 10 minutes after changing (editing) a simulation parameter (the "Simulation value" parameter is the exception), the simulation is automatically disabled and the device returns to normal measuring mode. When a timeout occurs, the "Simulation mode" parameter switches to "Disabled"...
  • Page 145: Simulate Ramp Function

    Parameter assignment 9.3 Parameter assignment over remote operation 9.3.4.2 Simulate ramp function Procedure To simulate a ramp function via remote operation (e.g. SIMATIC PDM), follow these steps: 1. For the "Simulation mode" parameter, set the "Ramp" option to simulate a changing pressure value.
  • Page 146: Customized Characteristic Curve

    Parameter assignment 9.3 Parameter assignment over remote operation End diagnostics simulation You close the simulation in the "Diagnostics simulation" tab: ● To disable a specific diagnostic action, click "Off" (under the "Action" field). ● To end the diagnostics simulation, click on the "Disable" button. NOTICE The device display shows a simulated diagnostic status and does not react to diagnostic events of normal operation.
  • Page 147: Custom Units" Parameter

    Parameter assignment 9.3 Parameter assignment over remote operation x values: 0%, 25%, 50%, 75%, 100% y values: 0%, 25%, 50%, 75%, 100% 9.3.5.2 "Custom units" parameter Selects a custom unit. The selected unit is displayed in the measurement view (Page 73). Setting range: Up to 12 characters Factory setting:...
  • Page 148: Sensor Calibration

    Parameter assignment 9.3 Parameter assignment over remote operation See also Application [05] (Page 106) 9.3.6 Sensor calibration You use the sensor trim to set the characteristic curve of the device at two trim points. The results are then correct measured values at the sensor trim points. The sensor trim points can be selected as any points within the nominal range.
  • Page 149: Diagnostics Functions

    Parameter assignment 9.3 Parameter assignment over remote operation Sensor trim at the upper trim point 1. Apply the pressure for the upper sensor trim at the device. The upper trim point needs to be greater than the lower trim point. 2.
  • Page 150 Parameter assignment 9.3 Parameter assignment over remote operation Configuring variables for monitoring Configure a process value for each "Limit monitoring" tab. Select the process value to be monitored in the "Monitored value" drop-down list. Enter the values for upper limit, lower limit and hysteresis that trigger an event.
  • Page 151 Parameter assignment 9.3 Parameter assignment over remote operation B:Lower limit with hysteresis An underrun event is counted when the process value falls below the lower limit (1). The next underrun event is counted when the process value first rises above the lower limit plus hysteresis (2), and then falls below the lower limit (3).
  • Page 152: Trend Log

    Parameter assignment 9.3 Parameter assignment over remote operation Enable monitoring Once the monitored variable is configured, you must ensure that the limit monitoring is set to Enabled and then select Apply and transfer to the device. To monitor a different process value, repeat the steps in a new tab page for limit monitoring.
  • Page 153: Functional Safety

    Functional Safety Introduction This section includes the required additional information for parameter assignment, commissioning and maintenance of the device in a safety-instrumented system. 10.1 Safety concept The device was developed in accordance with the Safety Integrity Level (SIL), which is defined as a relative level of risk reduction offered by a safety function.
  • Page 154: Safety Function

    Safety allowance The diagnostics function reacts within 2 seconds after detection of an error. Note For use outside the standard reference conditions, contact Siemens to define an additional safety accuracy. SITRANS P320/P420 (mA/HART) Operating Instructions, 06/2018, A5E44852162-AA...
  • Page 155 Functional Safety 10.1 Safety concept See also Remote seal (Page 37) Safety-instrumented system in single-channel operation (SIL 2) Automation system Final controlling Transmitter Figure 10-1 Safety-instrumented system in single-channel operation The combination of pressure transmitter, automation system and final controlling element forms a safety-instrumented system that performs fail-safe behavior.
  • Page 156: Device Statuses

    Functional Safety 10.1 Safety concept The automation system program must monitor the measured values of both SITRANS P devices. As soon as the measured values differ by e.g. 2% or more, the system must be brought into the safe state and the fault must be located. Two SITRANS P devices are required for multi-channel operation for SIL 3.
  • Page 157: Operating Modes Of The Device

    Functional Safety 10.1 Safety concept See also Certificates (Page 248) 10.1.4 Operating modes of the device The device can be operated as follows: ● "Functional Safety disabled" is used for operation in non-safety-related applications. ● "Functional Safety enabled" is used for operation in safety-related applications. See also Enabling Functional Safety (Page 160) 10.1.5...
  • Page 158: Validation

    Functional Safety 10.1 Safety concept When Functional Safety is enabled, the following device modes are displayed via the display or remote operation: Device mode Description Current output value Safe current output Functional Safety ena‐ Ensures safe measure‐ Operating signal bled ment output at the cur‐...
  • Page 159: Safety-Related Parameters

    Functional Safety 10.1 Safety concept 10.1.5.2 Safety-related parameters The following parameters are the safety-related parameters of the device: Parameter ID Parameter name on Meaning the display PV SELECT Pressure is the primary variable. The parameter cannot be changed. DAMPING Damping value [04] (Page 105) UPPER RANGE Set upper range value parameter [03] (Page 104) LOWER RANGE...
  • Page 160: Enabling Functional Safety

    Functional Safety 10.2 Enabling Functional Safety 10.2 Enabling Functional Safety You enable or disable Functional Safety with the "Functional Safety" wizard. The wizard is available via the device with a display and via remote operation (e.g. with the "Device > Functional Safety" menu command in SIMATIC PDM). For a device without display, enable Functional Security via remote operation.
  • Page 161 Functional Safety 10.2 Enabling Functional Safety Procedure 1. Navigate into the parameter view. Navigating in the views (Page 71) 2. Select the parameter "Functional Safety" [29]. 3. To start the wizard, enter the user PIN if needed. 4. Use the button to confirm.
  • Page 162 Functional Safety 10.2 Enabling Functional Safety 4. To complete validation of the safety-related parameters, confirm with YES. 5. To validate the fail-safe behavior, start the function test with "START". When you select "SKIP", you skip the function test and enable Functional Safety directly without validation of the fail-safe behavior.
  • Page 163: Enabling Functional Safety Over Remote Operation

    Functional Safety 10.2 Enabling Functional Safety Result The device is in the "Functional Safety enabled" device mode. ● The "SIL" symbol is displayed. ● The "DSABL" command appears (Disable Functional Safety). ● All parameters are protected against changes. ● When a safety-related error is detected on the device, the device changes to "Safety critical error"...
  • Page 164 Functional Safety 10.2 Enabling Functional Safety Procedure 1. Select the menu command "Functional Safety". 2. Enter the user PIN. SITRANS P320/P420 (mA/HART) Operating Instructions, 06/2018, A5E44852162-AA...
  • Page 165 Functional Safety 10.2 Enabling Functional Safety 3. Validate the following settings: – Identification data of your device: Long tag, product name, serial number. – Settings of the safety-related parameters To change the settings, exit the wizard with "Cancel". 4. Write down the fingerprint. Whenever you start the validation, the device generates a fingerprint.
  • Page 166 Functional Safety 10.2 Enabling Functional Safety 5. To confirm the validation, enter the validation key. 6. To validate the fail-safe behavior, start the function test. The device changes to the "Safety validation" device mode. 7. Confirm with "OK". Validate fail-safe behavior 1.
  • Page 167 Functional Safety 10.2 Enabling Functional Safety 3. Enter the user PIN. 4. Validate the identification data of your device. 5. Check that the displayed fingerprint matches the fingerprint you have written down. 6. Confirm the successful function test. Result The device is in the "Functional Safety enabled" device mode. ●...
  • Page 168: Acknowledging Safety-Related Errors

    Functional Safety 10.3 Acknowledging safety-related errors 10.3 Acknowledging safety-related errors 10.3.1 "Safety critical error" device mode Introduction When a safety-related error is detected on the device, the current output signal corresponds to the fault current and the diagnostic message is displayed. Figure 10-3 Parameter view of the display Acknowledge the safety-related error with the "Functional Safety"...
  • Page 169: Acknowledging Safety-Related Errors Via Remote Operation

    Functional Safety 10.3 Acknowledging safety-related errors 10.3.2 Acknowledging safety-related errors via remote operation Procedure 1. Select the menu command "Functional Safety". 2. Enter the user PIN. 3. Validate the identification data of your device: Long tag, product name and serial number. 4.
  • Page 170: Disabling Functional Safety Over Device With Display

    Functional Safety 10.4 Disabling Functional Safety over device with display 5. Validate the identification data of your device again: Long tag, product name and serial number. 6. Click "Ok". Functional Safety is disabled. The device restarts automatically. Result ● The safety-related error is acknowledged. ●...
  • Page 171: Disabling Functional Safety Over Remote Operation

    Functional Safety 10.5 Disabling Functional Safety over remote operation Procedure 1. Navigate into the parameter view. Navigating in the views (Page 71) 2. Select the parameter "Functional Safety" [29]. 3. Enter the user PIN. The wizard starts. 4. Select YES immediately and confirm wit the button.
  • Page 172: Proof Test

    Functional Safety 10.6 Proof test Result The device is in the "Functional Safety disabled" device mode. Note The system shows unexpected data or behaves differently than described in this procedure. ● Repeat the entire procedure. 10.6 Proof test Proof tests can detect errors in the device that are not detected by the integrated diagnostics of the device.
  • Page 173: Documenting A Proof Test

    Errors that are of critical importance for Functional Safety must be reported to Siemens Technical Support (Page 247). 10.7 Repair and service NOTICE Repair and service Repair and service work may only be performed by personnel authorized by Siemens. SITRANS P320/P420 (mA/HART) Operating Instructions, 06/2018, A5E44852162-AA...
  • Page 174 Functional Safety 10.7 Repair and service SITRANS P320/P420 (mA/HART) Operating Instructions, 06/2018, A5E44852162-AA...
  • Page 175: Service And Maintenance

    Service and maintenance 11.1 Basic safety instructions WARNING Use of a computer in a hazardous area If the interface to the computer is used in the hazardous area, there is a risk of explosion. ● Ensure that the atmosphere is explosion-free (hot work permit). WARNING Dust layers above 5 mm Risk of explosion in hazardous areas.
  • Page 176: Cleaning

    Service and maintenance 11.2 Cleaning 11.2 Cleaning 11.2.1 Cleaning the enclosure Cleaning the enclosure ● Clean the outside of the enclosure with the inscriptions and the display window using a cloth moistened with water or a mild detergent. ● Do not use any aggressive cleansing agents or solvents, e.g. acetone. Plastic parts or the painted surface could be damaged.
  • Page 177: Maintenance And Repair Work

    Service and maintenance 11.3 Maintenance and repair work 11.3 Maintenance and repair work CAUTION Hot surfaces Risk of burns during maintenance work on parts having surface temperatures exceeding 70 °C (158 °F). ● Take corresponding protective measures, for example by wearing protective gloves. ●...
  • Page 178: Checking The Gaskets

    Incorrect measured values will be displayed. Changing the seals in a process flange of a differential pressure measuring cell can alter the start-of-scale value. ● Changing seals in devices with differential pressure measuring cells may only be carried out by personnel authorized by Siemens. Note Using the wrong seals Using the wrong seals with flush-mounted process connections can cause measuring errors and/or damage the diaphragm.
  • Page 179: Check Cable Glands

    Service and maintenance 11.3 Maintenance and repair work 11.3.3 Check cable glands ● Check the tightness of the cable glands at regular intervals. ● Tighten the cable glands if necessary. SITRANS P320/P420 (mA/HART) Operating Instructions, 06/2018, A5E44852162-AA...
  • Page 180: Return Procedure

    Enclose the bill of lading, return document and decontamination certificate in a clear plastic pouch and attach it firmly to the outside of the packaging. Required forms ● Delivery note ● Return document (http://www.siemens.com/processinstrumentation/returngoodsnote) with the following information: – Product (item description) – Number of returned devices/replacement parts –...
  • Page 181: Diagnostics And Troubleshooting

    The symbols used for the display are based on NAMUR status signals, while the symbols used in SIMATIC PDM are based on standard diagnostic classes from Siemens. Note Priority conflict in the device status – NAMUR vs. Siemens standard A priority conflict can arise when multiple diagnostic events are pending at the same time.
  • Page 182 Diagnostics and troubleshooting 12.1 Device status symbols Device status symbols Display NAMUR SIMATIC PDM/PLC – NAMUR NE 107 – HCF Symbol Device status Priority * Priority * Symbol Device status Priority * Failure Maintenance alarm Cause: Output signal invalid due to fault in the field device or in the peripherals. Measure: Maintenance is required immediately.
  • Page 183 Cause: Measure: * The smallest number indicates the highest level of error severity. ** In SIMATIC PDM, the Siemens standard symbol as well as the corresponding NA\ symbol is displayed (by the device display). SITRANS P320/P420 (mA/HART) Operating Instructions, 06/2018, A5E44852162-AA...
  • Page 184: Diagnostic Messages

    Diagnostics and troubleshooting 12.2 Diagnostic messages 12.2 Diagnostic messages The following table shows the IDs of diagnostic messages and possible causes and instructions for corrective actions. Symbols Message Cause/Remedy Event counter 1 The number of overruns of the process value (set in parameters "Upper limit"...
  • Page 185 Diagnostics and troubleshooting 12.2 Diagnostic messages Symbols Message Cause/Remedy Event counter 2 The number of underruns of the process value (set in parameters "Lower limit" and "Monitored value") has reached the threshold. Number underruns above threshold Reset and acknowledge event counter. Maintenance required Check process conditions.
  • Page 186 Diagnostics and troubleshooting 12.2 Diagnostic messages Symbols Message Cause/Remedy Limit monitoring 1 Monitored value is above limit (set in parameter "Upper limit"). Above limit Limit monitoring 1 Monitored value is below limit (set in parameter "Lower limit"). Below limit Limit monitoring 2 Monitored value is above limit (set in parameter "Upper limit").
  • Page 187 Diagnostics and troubleshooting 12.2 Diagnostic messages Symbols Message Cause/Remedy Event counter 2 The number of underruns of the process value (set in parameters "Lower limit" and "Monitored value") has reached the threshold. Number underruns above threshold Reset and acknowledge event counter. Maintenance alarm Check process conditions.
  • Page 188 Diagnostics and troubleshooting 12.2 Diagnostic messages Symbols Message Cause/Remedy Loop current read back er‐ The loop current does not correspond to the expected value. Check DAC trim settings. Restore to factory DAC calibration. If the problem persists, contact Technical Support. Process conditions out‐...
  • Page 189 Diagnostics and troubleshooting 12.2 Diagnostic messages Symbols Message Cause/Remedy Safety validation mode Device is in safety validation mode. Complete the functional test and confirm that it was successful in the Func‐ tional Safety wizard. Safety critical device error Acknowledge the error in menu "Functional Safety" and enable Functional Safety mode.
  • Page 190: Troubleshooting

    Diagnostics and troubleshooting 12.3 Troubleshooting 12.3 Troubleshooting 12.3.1 Troubleshooting Functional Security Below you can find explanations on how to correct problems when enabling Functional Safety. Information mes‐ Cause of error Remedy sage on the dis‐ play INVALID CFG Write protection via user PIN disabled. Activate write protection via the user PIN.
  • Page 191: Technical Data

    Technical data 13.1 Input 13.1.1 Gauge pressure Gauge pressure input Measured variable Gauge pressure Measuring span (continuous‐ Measuring span Maximum permissible Maximum test ly adjustable) or measuring operating pressure MAWP pressure range, max. operating pres‐ (PS) sure (in accordance with 8.3 …...
  • Page 192: Gauge Pressure With Front-Flush Diaphragm

    Technical data 13.1 Input Gauge pressure measuring limits 30 mbar a/3 kPa a/0.44 psi a ● Measuring cell with inert oil 100 mbar a/10 kPa a/1.45 psi a ● Measuring cell with FDA-compliant oil Upper measuring limit 100% of max. range (for oxygen measurement: max. 100 bar/10 MPa/ 1450 psi and 60 °C ambient temperature/medium temperature) Start of scale value Between the measuring limits (continuously adjustable)
  • Page 193: Gauge Pressure From The Differential Pressure Series

    Technical data 13.1 Input 13.1.3 Gauge pressure from the differential pressure series Gauge pressure input from the differential pressure series Measured variable Gauge pressure and differential pressure Measuring span (continuous‐ Measuring span Maximum permissible Max. permissible ly adjustable) and maximum operating pressure test pressure operating pressure (accord‐...
  • Page 194: Absolute Pressure From The Gauge Pressure Series

    Technical data 13.1 Input 13.1.4 Absolute pressure from the gauge pressure series Absolute pressure input from the gauge pressure series Measured variable Absolute pressure Measuring span (continuous‐ Measuring span Maximum permissible Maximum test ly adjustable) or measuring operating pressure MAWP pressure range, max.
  • Page 195: Absolute Pressure With Front-Flush Diaphragm

    Technical data 13.1 Input Absolute pressure measuring limits from gauge pressure series Upper measuring limit 100% of max. range (for oxygen measurement: max. 100 bar/10 MPa/ 1450 psi and 60 °C ambient temperature/medium temperature) Lower range value Between the measuring limits (continuously adjustable) 13.1.5 Absolute pressure with front-flush diaphragm Absolute pressure with front-flush diaphragm...
  • Page 196: Absolute Pressure From The Differential Pressure Series

    Technical data 13.1 Input 13.1.6 Absolute pressure from the differential pressure series Absolute pressure input from the differential pressure series Measured variable Absolute pressure Measuring span (continuous‐ Measuring span Maximum permissible Max. permissible ly adjustable) and maximum operating pressure test pressure operating pressure (accord‐...
  • Page 197: Differential Pressure And Flow

    Technical data 13.1 Input 13.1.7 Differential pressure and flow Differential pressure input and flow Measured variable Differential pressure and flow Measuring span (continuous‐ Measuring span Maximum permissible Max. permissible ly adjustable) and maximum operating pressure test pressure operating pressure (accord‐ MAWP (PS) ing to 2014/68/EU Pressure 1 ...
  • Page 198: Level

    Technical data 13.1 Input Differential pressure and flow measuring limits Lower measuring limit -100% of maximum measuring range or 30 mbar a /3 kPa a /0.44 psi a ● Measuring cell with silicone oil filling ● Measuring cell with inert oil For process temperature -20 °C -100% of maximum measuring range or 30 mbar a /3 kPa a /0.44 psi a <...
  • Page 199: Measuring Accuracy Of Sitrans P320

    Technical data 13.2 Measuring accuracy of SITRANS P320 Level measuring limits Lower measuring limit Measuring cell with silicone oil -100% of max. measuring range or 30 mbar a/3 kPa a/0.44 psi a depending filling on the mounting flange Measuring cell with inert oil -100% of max.
  • Page 200 Technical data 13.2 Measuring accuracy of SITRANS P320 Conformity error at limit point setting, including hysteresis and repeatability - gauge pressure 1 bar/100 kPa/14.5 psi ≤ 0.065% ≤ (0.004 • r + 0.045)% 4 bar/400 kPa/58 psi 16 bar/1.6 MPa/232 psi 63 bar/6.3 MPa/914 psi 160 bar/16 MPa/12321 psi r ≤...
  • Page 201: Gauge Pressure From The Differential Pressure Series

    Technical data 13.2 Measuring accuracy of SITRANS P320 13.2.4 Gauge pressure from the differential pressure series Conformity error at limit point setting, including hysteresis and repeatability - gauge pressure from the differential pressure series Measuring span ratio r (spread, Turn-Down) r = max.
  • Page 202: Absolute Pressure From Gauge And Differential Pressure Series

    Technical data 13.2 Measuring accuracy of SITRANS P320 Step response time T (without electrical damping) - gauge pressure from differential pressure series 20 mbar/2 kPa/8.031 inH Approx. 0.160 s 60 mbar/6 kPa/24.09 inH2O Approx. 0.150 s 250 mbar/25 kPa/3.6 psi Approx.
  • Page 203: Absolute Pressure With Front-Flush Diaphragm

    Technical data 13.2 Measuring accuracy of SITRANS P320 Step response time T (without electrical damping) - absolute pressure from gauge and differential pressure series Gauge pressure series All measuring cells Approx. 0.105 s Differential pressure series 250 mbar/25 kPa/3.6 psi Approx.
  • Page 204: Gauge Pressure With Front-Flush Diaphragm

    Technical data 13.2 Measuring accuracy of SITRANS P320 Effect of mounting position In pressure per change of angle 0.04 kPa/0.4 mbar/0.006 psi per 10° incline (zero-point correction is possible with position error compen‐ sation) 13.2.7 Gauge pressure with front-flush diaphragm Conformity error at limit point setting, including hysteresis and repeatability - gauge pressure with front-flush diaphragm Measuring span ratio r (spread, Turn-Down) r = max.
  • Page 205: Differential Pressure And Flow

    Technical data 13.2 Measuring accuracy of SITRANS P320 13.2.8 Differential pressure and flow Conformity error at limit point setting, including hysteresis and repeatability - differential pressure and flow Measuring span ratio r (spread, Turn-Down) r = max. measuring span/set measuring span and nomi‐ nal measuring range Linear characteristic curve r ≤...
  • Page 206 Technical data 13.2 Measuring accuracy of SITRANS P320 Conformity error at limit point setting, including hysteresis and repeatability - differential pressure and flow Flow 25 ... 50% 250 mbar/25 kPa/3.63 psi ≤ 0.13% ≤ (0.008 • r + 0.09)% 600 mbar/60 kPa/8.70 psi 1600 mbar/160 kPa/23.21 psi 5 bar/500 kPa/72.52 psi 30 bar/3 MPa/435.11 psi...
  • Page 207 Technical data 13.2 Measuring accuracy of SITRANS P320 Long-term stability at ±30 °C (±54 °F) - differential pressure and flow 250 mbar/25 kPa/3.63 psi In 5 years ≤ (0.125 • r)% 600 mbar/60 kPa/8.70 psi In 10 years ≤ (0.15 • r)% 1600 mbar/160 kPa/23.21 psi 5 bar/500 kPa/72.52 psi 30 bar/3 MPa/435.11 psi...
  • Page 208: Level

    Technical data 13.2 Measuring accuracy of SITRANS P320 13.2.9 Level Conformity error at limit point setting, including hysteresis and repeatability - level Measuring span ratio r (spread, r = max. measuring span/set measuring span and nominal measuring range Turn-Down) ● Linear characteristic curve r ≤...
  • Page 209: Measuring Accuracy Of Sitrans P420

    Technical data 13.3 Measuring accuracy of SITRANS P420 13.3 Measuring accuracy of SITRANS P420 13.3.1 Reference conditions ● According to EN 60770-1/IEC 61298-1 ● Rising characteristic curve ● Lower range value 0 bar/kPa/psi ● Seal diaphragm stainless steel ● Measuring cell with silicone oil filling ●...
  • Page 210: Gauge Pressure From The Differential Pressure Series

    Technical data 13.3 Measuring accuracy of SITRANS P420 Effect of ambient temperature - gauge pressure 4 bar/400 kPa/58 psi ≤ (0.025 • r + 0.125)% 16 bar/1.6 MPa/232 psi 63 bar/6.3 MPa/914 psi 160 bar/16 MPa/2321 psi 400 bar/40 MPa/5802 psi 700 bar/70 MPa/10152 psi ≤...
  • Page 211 Technical data 13.3 Measuring accuracy of SITRANS P420 Conformity error at limit point setting, including hysteresis and repeatability - gauge pressure from differential pressure series 250 mbar/25 kPa/3.6 psi ≤ 0.04% ≤ (0.004 • r + 0.045)% 600 mbar/60 kPa/240.9 inH 1600 mbar/160 kPa/642.4 inH 5000 mbar/500 kPa/2008 inH 30 bar/3 MPa/435 psi...
  • Page 212: Absolute Pressure From Gauge And Differential Pressure Series

    Technical data 13.3 Measuring accuracy of SITRANS P420 Effect of mounting position ≤ 0.7 mbar/0.007 kPa/0.01015266 psi per 10° incline (zero-point correction is possible with position error compen‐ sation) 13.3.5 Absolute pressure from gauge and differential pressure series Conformity error at limit point setting, including hysteresis and repeatability - absolute pressure from gauge and differential pressure series Measuring span ratio r (spread, Turn-Down) r = max.
  • Page 213: Absolute Pressure With Front-Flush Diaphragm

    Technical data 13.3 Measuring accuracy of SITRANS P420 Effect of mounting position - absolute pressure from gauge and differential pressure series In pressure per change of angle ● For absolute pressure (from the gauge pressure series): ≤ 0.05 mbar/0.005 kPa/0.000725 psi per 10° incline ●...
  • Page 214: Gauge Pressure With Front-Flush Diaphragm

    Technical data 13.3 Measuring accuracy of SITRANS P420 13.3.7 Gauge pressure with front-flush diaphragm Conformity error at limit point setting, including hysteresis and repeatability - gauge pressure with front-flush diaphragm Measuring span ratio r (spread, Turn-Down) r = max. measuring span/set measuring span and nominal measuring range ●...
  • Page 215 Technical data 13.3 Measuring accuracy of SITRANS P420 Conformity error at limit point setting, including hysteresis and repeatability - differential pressure and flow Linear characteristic curve r ≤ 5 5 < r ≤ 60 60 mbar/6 kPa/0.87 psi ≤ 0.075% ≤...
  • Page 216 Technical data 13.3 Measuring accuracy of SITRANS P420 Conformity error at limit point setting, including hysteresis and repeatability - differential pressure and flow Flow 25 ... 50% ≤ 0.08% ≤ (0.008 • r + 0.09)% ● 250 mbar/25 kPa/3.63 psi 600 mbar/60 kPa/8.70 psi 1600 mbar/160 kPa/23.21 psi 5 bar/500 kPa/72.52 psi...
  • Page 217 Technical data 13.3 Measuring accuracy of SITRANS P420 Long-term stability at ±30 °C (±54 °F) - differential pressure and flow 250 mbar/25 kPa/3.63 psi In 5 years ≤ (0.125 • r)% 600 mbar/60 kPa/8.70 psi In 10 years ≤ (0.15 • r)% 1600 mbar/160 kPa/23.21 psi 5 bar/500 kPa/72.52 psi 30 bar/3 MPa/435.11 psi...
  • Page 218: Level

    Technical data 13.3 Measuring accuracy of SITRANS P420 13.3.9 Level Conformity error at limit point setting, including hysteresis and repeatability - level Measuring span ratio r (spread, r = max. measuring span/set measuring span and nominal measuring range Turn-Down) ● Linear characteristic curve r ≤...
  • Page 219: Output

    Technical data 13.5 Operating conditions 13.4 Output Output HART Output signal 4 … 20 mA ● Low saturation limit (continuously 3.55 mA, set to 3.8 mA in the factory adjustable) 22.8 mA, factory-set to 20.5 mA or optionally 22.0 mA ●...
  • Page 220 Technical data 13.5 Operating conditions Operating conditions for gauge pressure and absolute pressure (from the gauge pressure series) Enclosure Measuring cell with sili‐ -40 … +85 °C (-40 … +185 °F) cone oil filling Measuring cell with inert -40 ... +85 °C (-40 ...+185 °F) oil for gauge pressure measuring cells 1, 4, 16 and 63 bar...
  • Page 221 Technical data 13.5 Operating conditions Operating conditions for gauge pressure and absolute pressure with flush-mounted diaphragm Ambient conditions ● Ambient temperature Note Observe the temperature class in hazardous areas. Enclosure Measuring cell with sili‐ -40 … +85 °C (-40 … +185 °F) cone oil filling Measuring cell with inert 1 bar/100 kPa/3.6 psi...
  • Page 222 Technical data 13.5 Operating conditions Operating conditions for gauge pressure and absolute pressure (from the differential pressure series), differential pressure and flow rate Installation conditions ● Installation instruction Ambient conditions ● Ambient temperature Note Observe the temperature class in hazardous areas. Enclosure Measuring cell with sili‐...
  • Page 223 Technical data 13.5 Operating conditions Operating conditions for gauge pressure and absolute pressure (from the differential pressure series), differential pressure and flow rate Measuring cell with FDA- -10 ... +100°C (14 ...+212°F) compliant oil In conjunction with dust -40 … +85 °C (-4 … +185 °F) explosion protection Operating conditions for level Installation conditions...
  • Page 224: Vibration Resistance

    Technical data 13.6 Vibration resistance 13.6 Vibration resistance General operating conditions Gauge pressure series Differential pressure series Aluminum and stainless steel enclosure Aluminum and stainless steel enclosure Vibrations (sine) 2 ... 9 Hz at 0.3 mm IEC 60068-2-6 9 ... 200 Hz at 5 m/s² 1 octave/min 5 cycles/axis Continuous shocks (half-sine)
  • Page 225: Construction

    Technical data 13.7 Construction Operating conditions according to IEC Differential pressure series 61298-3 (5g enhanced) Aluminum and stainless steel enclosure Vibrations (sine) 10 ... 58 Hz at 0.7 mm IEC 60068-2-6 58 ... 1000 Hz at 50 m/s² 1 octave/min 20 cycles/axis 1) Without mounting bracket Operating conditions for marine (only in...
  • Page 226 Technical data 13.7 Construction Construction for gauge pressure and absolute pressure (from the gauge pressure series) Process connection ● Connection pin G A in accordance with DIN EN 837-1 ● Female thread ‑14 NPT ● Oval flange (PN 160 (MAWP 2320 psi g)) with fastening screw thread: –...
  • Page 227 Technical data 13.7 Construction Construction for gauge pressure and absolute pressure (from the differential pressure series), differential pressure and flow rate Weight Approx. 3.9 kg (8.5 lb) with aluminum enclosure Approx. 5.9 kg (13 lb) with stainless steel enclosure Material ●...
  • Page 228 Technical data 13.7 Construction Construction for level Stainless steel, mat. no. 1.4404/316L, Monel 400, mat. no. 2.4360, Alloy B2, mat. ● Seal diaphragm on the no. 2.4617, Alloy C276, mat. no. 2.4819, Alloy C22, mat. no. 2.4602, tantalum, PTFE mounting flange Smooth as per EN 1092‑1, form B1 or ASME B16.5 RF 125 …...
  • Page 229: Torques

    Technical data 13.9 Display, keyboard and auxiliary power 13.8 Torques Torques Cable glands/blanking plugs 4 Nm (3 ft lb) ● Screw-in torque for plastic gland in all enclosures 6 Nm (4.4 ft lb) ● Screw-in torque for metal/stainless steel glands in aluminum/stainless steel enclosure 15 Nm (11.1 ft lb) ●...
  • Page 230: Certificates And Approvals

    Technical data 13.10 Certificates and approvals 13.10 Certificates and approvals Certificates and approvals Classification according to pressure equipment direc‐ ● For gases of fluid group 1 and liquids of fluid group 1; complies tive (PED 2014/68/EU) with requirements of article 4, paragraph 3 (sound engineering practice) ●...
  • Page 231 Technical data 13.10 Certificates and approvals Certificates and approvals Designation II 1D Ex tb IIIC T120 °C Da II 2D Ex tb IIIC T120 °C Db II 3D Ex tc IIIC T120 °C Dc Permissible ambient temperature -40 ... +80 °C (-40 ... +176 °F) Permissible temperature of medium -40 …...
  • Page 232 Technical data 13.10 Certificates and approvals SITRANS P320/P420 (mA/HART) Operating Instructions, 06/2018, A5E44852162-AA...
  • Page 233: Dimension Drawings

    Dimension drawings 14.1 SITRANS P320/P420 for gauge pressure and absolute pressure from the gauge pressure series approx. 96 (3.78) 17 (0.67) 105 (4.13) ① Electronics side, display (longer for cover with inspection window) ② Connection end ③ Electrical connection: ● M20 x 1.5 gland ●...
  • Page 234 Dimension drawings 14.1 SITRANS P320/P420 for gauge pressure and absolute pressure from the gauge pressure series Not with "flameproof enclosure" type of protection Not for "FM + CSA [is + XP]" type of protection Figure 14-1 SITRANS P320 and SITRANS P420 pressure transmitters for absolute pressure, from the gauge pressure series, dimensions in mm (inches) SITRANS P320/P420 (mA/HART) Operating Instructions, 06/2018, A5E44852162-AA...
  • Page 235: Sitrans P320/P420 For Differential Pressure, Gauge Pressure, Flow And Absolute Pressure From The Differential Pressure Series

    Dimension drawings 14.2 SITRANS P320/P420 for differential pressure, gauge pressure, flow and absolute pressure from the differential pressure series 14.2 SITRANS P320/P420 for differential pressure, gauge pressure, flow and absolute pressure from the differential pressure series ① Electronics side, display (longer for cover with inspection window) ②...
  • Page 236 Dimension drawings 14.2 SITRANS P320/P420 for differential pressure, gauge pressure, flow and absolute pressure from the differential pressure series Figure 14-2 SITRANS P320 and SITRANS P420 pressure transmitters for differential pressure and flow, dimensions in mm (inches) 146 (5.75) approx. 96 (3.78) 84 (3.31) 17 (0.67) 27 (1.06)
  • Page 237: Sitrans P 320/P420 For Level

    Dimension drawings 14.3 SITRANS P 320/P420 for level 14.3 SITRANS P 320/P420 for level 27 (1.06) 84 (3.31) 146 (5.75) 29 (1.14) 74 (2.31) 61 (2.4) 135 (5.31) min. 92 (3.62) 108 (4.25) 54 (2.13) n x d 17 (0.67) approx.
  • Page 238: Sitrans P320/P420 (Front-Flush)

    Dimension drawings 14.4 SITRANS P320/P420 (front-flush) Not with "flameproof enclosure" type of protection Not for "FM + CSA [is + XP]" type of protection Figure 14-4 SITRANS P320 and SITRANS P420 pressure transmitters for level, including mounting flange, dimensions in mm (inch) 14.4 SITRANS P320/P420 (front-flush)
  • Page 239: Note 3A And Ehdg

    Dimension drawings 14.4 SITRANS P320/P420 (front-flush) 14.4.1 Note 3A and EHDG Note Approvals The references to the approvals for "EHEDG" and "3A" refer to the respective process connections and are not device-specific. Please refer to the technical specifications of the respective pressure transmitter to see whether the desired certificate is available for your device/flange combination.
  • Page 240: F&B And Pharma Flange

    Dimension drawings 14.4 SITRANS P320/P420 (front-flush) Flange according to ASME ASME B 16.5 CLASS ⊘D 110 mm (4.3'') Approx. 52 mm (2'') 1½" 125 mm (4.9'') 1½" 155 mm (6.1'') 150 mm (5.9'') 165 mm (6.5'') 190 mm (7.5'') 210 mm (8.1'') 230 mm (9.1'') 255 mm (10.0'') 14.4.3...
  • Page 241 Dimension drawings 14.4 SITRANS P320/P420 (front-flush) DIN 11864-2 Form A - sterile collar flange ⊘D 94 mm (3.7'') Approx. 52 mm (2'') 113 mm (4.4'') 133 mm (5.2'') 159 mm (6.3'') Approvals EHEDG DIN 11864-2 Form A - sterile groove flange ⊘D 94 mm (3.7'') Approx.
  • Page 242 Dimension drawings 14.4 SITRANS P320/P420 (front-flush) Other connections Varivent connector ® ⊘D 40-125 84 mm (3.3'') Approx. 52 mm (2'') Approvals EHEDG Connection in accordance with DRD ⊘D 105 mm (4.1'') Approx. 52 mm (2'') BioConnect connectors BioConnect screwed joint ⊘D 82 mm (3.2'') Approx.
  • Page 243 Dimension drawings 14.4 SITRANS P320/P420 (front-flush) BioConnect flange connector ⊘D 110 mm (4.3'') Approx. 52 mm (2'') 140 mm (5.5'') 150 mm (5.9'') 175 mm (6.9'') 2" 100 mm (3.9'') 2½" 110 mm (4.3'') 3" 140 mm (5.5'') 4" 175 mm (6.9'') Approvals EHEDG BioConnect...
  • Page 244: Pmc Style

    Dimension drawings 14.4 SITRANS P320/P420 (front-flush) Other connections BioControl connector ⊘D 90 mm (3.5'') Approx. 52 mm (2'') 120 mm (4.7'') Approvals EHEDG 14.4.4 PMC Style Connections for the paper industry PMC Style Standard ⊘D – – 40.9 mm (1.6'') Approx.
  • Page 245: Special Connections

    Dimension drawings 14.4 SITRANS P320/P420 (front-flush) 14.4.5 Special connections Tank connection TG52/50 and TG52/150 ⊘D TG52/50 63 mm (2.5'') Approx. 63 mm (2.5'') TG52/150 63 mm (2.5'') Approx. 170 mm (6.7'') SMS connectors SMS sockets with union nut ⊘D 2" 84 mm (3.3'') Approx.
  • Page 246 Dimension drawings 14.4 SITRANS P320/P420 (front-flush) IDF connectors IDF sockets with union nut ⊘D 2" 77 mm (3.0'') Approx. 52 mm (2.1'') 2½" 91 mm (3.6'') 3" 106 mm (4.2'') IDF threaded sockets ⊘D 2" 64 mm (2.5'') Approx. 52 mm (2.1'') 2½"...
  • Page 247: Appendix

    In addition to our documentation, Siemens provides a comprehensive support solution at: ● Service&Support (http://www.siemens.com/automation/service&support) Personal contact If you have additional questions about the device, please contact your Siemens personal contact at: ● Partner (http://www.automation.siemens.com/partner) To find the personal contact for your product, go to "All Products and Branches" and select "Products &...
  • Page 248: Certificates

    A.4 Checklist for Functional Safety Certificates You can find certificates on the Internet at Certificates (http://www.siemens.com/ processinstrumentation/certificates) or on an included DVD. QR code label A QR code label can be found on the device. With the use of a smart phone, the QR code provides a direct link to a website with information specific to the device, such as manuals, FAQs, certificates, etc.
  • Page 249 Appendix A.4 Checklist for Functional Safety Step 2: Validate values using the "Func‐ Values for the validation Enter validated value tional Safety" wizard ① Device identification data (if Function‐ The values can be found on the rat‐ al Safety is enabled via remote oper‐ ing plate of the device and are dis‐...
  • Page 250 Appendix A.4 Checklist for Functional Safety SITRANS P320/P420 (mA/HART) Operating Instructions, 06/2018, A5E44852162-AA...
  • Page 251: List Of Abbreviations

    List of abbreviations Pressure transmitter abbreviations List of abbreviations Table B-1 Units Abbrevi‐ Display in In full Meaning ation the edit view bar a bar absolute Pressure unit for absolute pressure bar g bar gauge Pressure unit for gauge pressure mbar mbar Millibars...
  • Page 252 US - American Fire Protection Organization F&B Food and beverage industry Engl.: Process Device Manager Tool for communication with HART devices (manufacturer: Siemens) Engl.: Upper Range Limit Upper end of the measuring range Engl.: Upper Range Value Upper end of the set measuring span...
  • Page 253: Glossary

    Glossary ATEX ATEX is an abbreviation of the French term "Atmosphère explosible" (potentially explosive atmosphere). ATEX stands for both EC directives in the area of explosion protection: ATEX product directive 94/9/EC and ATEX operating directive 1999/92/EC. Auxiliary power supply Auxiliary power supply refers to an electrical supply or reference voltage which some electrical circuits require apart from the standard supply.
  • Page 254 Glossary Fingerprint Numerical value generated by the device when you start safety validation via the "Functional Safety" wizard. By comparing the fingerprint, you determine whether or not the device and the safety-related parameters have changed erroneously during activation of the functional safety.
  • Page 255 Glossary Safety function Defined function executed by a safety-instrumented system with the objective of attaining or maintaining a safe system state by taking a defined hazardous incident into account. Example: Limit pressure monitoring Safety Integrity Level → Safety-instrumented system A safety-instrumented system (SIS) executes the safety functions that are required to achieve or maintain a safe state in a system.
  • Page 256 Glossary Total Performance Total Performance is the square root of the sum of the squares of the three deviations resulting from the influence of the static pressure, the temperature and the characteristic deviation. Total Performance → SITRANS P320/P420 (mA/HART) Operating Instructions, 06/2018, A5E44852162-AA...
  • Page 257: Index

    Index Documentation, 247 3A, 239 Edit view, 76 EHEDG, 239 Electromagnetic compatibility, 220, 221, 222, 223 EMC, 220, 221, 222, 223 ACCES ETEMP, 123 INVALID CFG, 190 Ambient temperature, 219, 221, 222, 223 Effect, 203, 213 Application, , (Transfer function) APPLY LRV, 75 Fail-safe behavior, 154 APPLY URV, 75...
  • Page 258 Index Overview of parameters and functions, 97 Laws and directives Disassembly, 19 PARAB, 108 Personell, 19 PARAE, 108 Layout of nameplate with general information, 26 PARAM LEVEL, 108, 123 INVALID CFG, 190 LEVEL UNITS, 75 Parameter view, 74 LO FAULT CUR, 75 PIN RECOVERY, 75 Load, 219 PRESS, 108...
  • Page 259 Index Square root function Hold at 0, square root, 111 Linear, square root, 111 Two step linear, square root, 112 Warranty, 17 Stabilizing valve, 91, 92, 93, 95 Write protection, 79 START VIEW, 75 Structure, 25 STSIM INVALID CFG, 190 Support, 247 ZERO POINT, 75 Support request, 247...
  • Page 260 Index SITRANS P320/P420 (mA/HART) Operating Instructions, 06/2018, A5E44852162-AA...