Siemens SITRANS P DS III Operating Instructions Manual page 181

Pressure transmitter with hart
Hide thumbs Also See for SITRANS P DS III:
Table of Contents

Advertisement

Differential pressure and flow rate input
Measured variable
Span (continuously
adjustable) or measuring
range and max. operating
pressure (in accordance
with 97/23/EC Pressure
Equipment Directive)
Lower measuring limit
Measuring cell with
silicone oil filling
Measuring cell with
inert liquid
SITRANS P DS III with HART
Operating Instructions, 06/2013, A5E00047092-09
HART
Differential pressure and flow rate
Span
Maximum operating
pressure MAWP (PS)
1 ... 20 mbar (0.4015
32 bar (464 psi)
... 8.031 inH
O)
2
1 ... 60 mbar (0.4015
160 bar (2320 psi)
... 24.09 inH
O)
2
2.5 ... 250 mbar
(1.004 ...
100.4 inH
O)
2
6 ... 600 mbar
(2.409 ... 240.9 inH
2
O)
16 ... 1600 mbar
(6.424 ...
642.4 inH
O)
2
50 ... 5000 mbar
(20.08 ...
2008 inH
O)
2
0.3 ... 30 bar
(4.35 ... 435 psi)
2.5 ... 250 mbar
420 bar (6091 psi)
(1.004 ...
100.4 inH
O)
2
6 ... 600 mbar
(2.409 ... 240.9 inH
2
O)
16 ... 1600 mbar
(6.424 ...
642.4 inH
O)
2
50 ... 5000 mbar
(20.08 ...
2008 inH
O)
2
0.3 ... 30 bar
(4.35 ... 435 psi)
-100% of max. measuring range
(-33 % for 30 bar (435 psi) measuring cell) or 30 mbar a (0.44 psi a)
PROFIBUS PA and FOUNDATION Fieldbus
Measuring range
Maximum operating
pressure
20 mbar
32 bar a (464 psi)
(8.031 inH
O)
2
60 mbar
160 bar (2320 psi)
(24.09 inH
O)
2
250 mbar
(100.4 inH
O)
2
600 mbar
(240.9 inH
O)
2
1600 mbar
(642.4 inH
O)
2
5 bar
(2008 inH
O)
2
30 bar
(435 psi)
250 mbar
420 bar (6091 psi)
(100.4 inH
O)
2
600 mbar
(240.9 inH
O)
2
1600 mbar
(642.4 inH
O)
2
5 bar
(2008 inH
O)
2
30 bar
(435 psi)
Technical data
11.2 Input point
181