Master Reset
A master reset is recommended before first configuring a new device. (Block Status must
be Out of Service to perform a Master Reset.)
1.
Navigate to Configure/Setup > Resource > Operation > Methods and click to open
the dialog window.
2.
In the General field, click on Master Reset and click Next to perform reset to factory
defaults. Click Next to accept default reset to Factory Defaults.
Master
Reset
3.
Click FINISH then restart AMS to reload settings. Next, scan the device.
Scan Device
Scan Device uploads parameters from the device (synchronizes parameters) to AMS
Device Manager.
1.
Open the pull-down menu Actions – Scan Device (upload parameters from the
device to AMS).
2.
The next step when adding a new device is to configure and calibrate the device via
the Quick Start Wizard.
Sensor calibration
The LR250 FF does not need to be calibrated, only configured using the Quick Start
Wizard below.
Configuring a new device
Configure a new device using the Quick Start Wizard, found in the Resource Block of the
function group Configure/Setup.