Commissioning
5.6 Setting basic functions
5.6.2

Configuring PROFIsafe

Setting the address
Procedure
To set the PROFIsafe address, proceed as follows:
1. In STARTER select the input field for the PROFIsafe address
2. Enter the same address as hexadecimal value, which you defined in the hardware
configuration (F_Dest_Add).
See also Section: Configuring PROFIBUS communication with telegram 30 via GSD
(Page 78).
You have configured the communication between the inverter and the higher-level control (F-
CPU) using PROFIsafe telegram 30.
Parameter
p9610
Enabling Shared Device
If you control the inverter safety functions via PROFINET and "Shared Device", you must
enable this function in the inverter.
See also Section: Configuring shared device communication via PROFINET (Page 82).
Procedure
To configure communication via "Shared Device" in the inverter, proceed as follows:
1. In STARTER change to the expert list.
2. In STARTER, set p8929 = 2.
You have configured the communication via "Shared Device" in the inverter.
92
Description
PROFIsafe address (factory setting: 0000 hex)
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 04/2014, FW V4.7, A5E34261271B AA