Commissioning
5.8 Offline commissioning
Loading the settings into an inverter using STARTER
Procedure
To load the settings to the inverter, proceed as follows:
1. Go online with STARTER and start to download to the inverter using the button
After the download, the inverter signals faults. Ignore these faults, as they will be
automatically acknowledged by the following steps.
2. Select the screen form for the safety functions.
3. Select the button to change the settings.
4. Activate the settings using the associated button.
5. Save your settings (copy RAM to ROM ).
6. Switch off the inverter supply voltage.
7. Wait until all of the LED on the inverter go dark.
8. Switch on the inverter supply voltage again.
The inverter has now accepted your settings.
154
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 04/2014, FW V4.7, A5E34261271B AA
.