Operation
6.8 Safe Direction (SDI)
The feedback signal "SDI active" for pulse inhibit remains active
Procedure
To switch the motor on, proceed as follows:
1. Select STO (or SS1).
2. Deselect STO (or SS1) again.
3. After deselecting STO, wait until the inverter is "ready to switch on".
Alternatively: After deselecting STO, wait a certain time before switching on. We
recommend a wait time of 200 ms.
4. Switch on motor within 5 s after deselecting STO (ON command).
Figure 6-43
You have switched on the motor again.
You have not switched on the motor within 5 seconds
If you do not switch on the motor within 5 seconds after deselecting STO, the following
happens:
● The inverter goes back into the STO state.
● The inverter no longer responds to the ON command.
● The inverter outputs Alarm A01795.
To switch on the motor you must repeat the procedure described above.
220
Switching the motor off and on when SDI is active
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 04/2014, FW V4.7, A5E34261271B AA