Wiring Examples; Connecting Sensors - Siemens SINAMICS G120 Function Manual

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Installing
4.3 Activation via F-DI
Special measures when establishing connections
When routing cables over longer distances, e.g. between remote control cabinets, you have
the following options to reduce the risk of damaged cables when your plant or machine is
operating:
● Use shielded cables with grounded shield.
● Lay signal cables in steel pipes.
4.3.2

Wiring examples

On the following pages, you will find examples of interconnecting safety digital inputs in
accordance with PL d to EN 13849-1 and SIL 2 to IEC 61508.
4.3.2.1

Connecting sensors

Electromechanical sensor
If there is a risk of cross-circuits or short-circuits, the cables between the sensor and the
inverter must be protected, for example, by routing them in a steel tube.
The inverter provides the supply voltage
1)
Figure 4-6
54
The 24 V supply is not required when using the G110M "24 V Power Module" option
Connecting an electromechanical sensor to the inverter power supply
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 04/2014, FW V4.7, A5E34261271B AA

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents